为解决埋弧矿热炉变压器中压补偿存在的不安全因素,较详细的介绍了保护方法的改进及注意事项。在一次设备方面应加装Z型接地变压器和设置消弧消谐装置;在二次设备方面应设置零序电流保护和增设变压器反限时过电流保护。经过如此保护,变压器运行稳定,企业生产效益显著。
According to the existing unsafe factors for submerged arc furnace transformer medium voltage compensation, this paper introduced the improvement of protection methods and the precautions. It should add Z-Type grounding transformer and set arc blow-out and harmonic elimination installation for primary equipment. Zero sequence current protection and additional transformer reverse time limit over current protection were be set on secondary equipment. After such a protection, transformer run stable, enterprise production benefit is remarkable.