新型三相三线电能表错接线快速判别方法研究 被引量:10

Study on the Rapid Error Connections Discriminating Method of the New Three-Phase and Three-Wire Measuring Device
下载PDF
导出
摘要 高压计量装置现场接线复杂,错误接线很难判别,且判别中算法复杂,无法快速准确的给出结果。通过现场简单测试电能表各计量元件之间的相位角度,作出各计量元件之间的相量图,通过整体旋转相量图的方式,快速判断出三相三线计量装置在感性负载和容性负载下的接线关系,实现三相三线电能表错接线的快速精确识别。 The result of the error connections can’t be obtained accurately and rapidly because of the complex of connections in the field and the criteria algorithm. The phasor diagram between the measuring components can be easily established according to the angle measured in the field. Wiring relations of inductive load and capacitive load can be determined quickly after the overall rotation of phasor diagram. So error connections of three - phase and three - wire measuring device can be discriminated quickly and accurately.
出处 《电测与仪表》 北大核心 2014年第13期5-8,共4页 Electrical Measurement & Instrumentation
基金 国家电网公司总部科技资助项目(国家电网发展[2013]170号52100113058L)
关键词 错接线 三相三线电能表 快速判别方法 error connections three-phase and three-wire measuring device rapid discriminating method