摘要
在作者前期研究的基础上 ,进一步研究了保证过冷水动态制冰系统中过冷却器不发生结冰的条件 ,建立了能够稳定运行的过冷水动态制冰实验装置。水在过冷却器入口的最低温度为 0 .45℃ ,在过冷却器中的温降约为 1 .0℃。
Further studies based on the authors' earlier researches the conditions under which no freezing occur in the supercooler while sufficient supercooling of water is guaranteed. Establishes a stably operating experimental assembly. Water temperature at the entrance of the supercooler reaches as low as 0.45 ℃, and the water temperature drop in supercooler is about 1 ℃.
出处
《暖通空调》
北大核心
2001年第2期1-4,共4页
Heating Ventilating & Air Conditioning
关键词
过冷水
动态制冰
过冷却器
防止
结冰
supercooled water, dynamic ice making, supercooler, icing prevention