期刊文献+

35 kV输电线路雷击特性及防雷措施研究 被引量:11

Analysis of Lightning Transient Characteristics and Lightning Protection Measures of 35 kV Overhead Line
原文传递
导出
摘要 35 kV输电线路因绝缘水平低,雷击电磁暂态特性与高电压等级输电线路有较大区别;线路防雷技术人员根据高电压等级线路避雷器的使用方法开展35 kV线路防雷,导致了避雷器频繁爆炸的问题。利用电磁暂态分析软件ATP-EMTP,对35 kV线路雷击特性进行了分析,提出了35 kV线路避雷器应多基杆塔多相导线同时安装的原则;通过对不同雷电流作用下线路避雷器能量吸收情况进行分析,说明了线路避雷器频繁爆炸的原因,提出了解决现有35 kV线路防雷问题的可行方案。 Due to low insulation level,the lightning electromagnetic transient characteristics of 35 kV transmission line are very difference from high voltage transmission line. Technicians carry out 35 kV line lightning protection based on the use of high voltage level line lightning arrester,resulting in frequent explosion of lightning arrester. In this paper,the electromagnetic transient analysis software ATP-EMTP was used in lightning characteristics analysis of 35 kV line. The line arrester should be multi tower and multi-phase installed in 35 kV line lightning protection. Based on the analysis of the energy absorption of line surge arrester under different lightning current,the reason of frequent explosion of line arrester is explained. A feasible scheme to solve the lightning protection problem of the existing 35 kV line is proposed. The results of this study have important reference value for the lightning protection of 35 kV line.
作者 刘守豹 曾伟 廖文龙 刘强 LIU Shoubao;ZENG Wei;LIAO Wenlong;LIU Qiang(Sichuan Water Conservancy Vocational College,Chengdu 611830,China;Siehuan Electric Power Industrial Adjustment Test Institute,Chengdu 610072,China)
出处 《电瓷避雷器》 CAS 北大核心 2018年第6期34-38,共5页 Insulators and Surge Arresters
关键词 雷击暂态 线路避雷器 架空避雷线 防雷措施 lightning transient line arrester overhead lightning conductor lightning protection measure
  • 相关文献

参考文献13

二级参考文献140

共引文献404

同被引文献134

引证文献11

二级引证文献30

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部