期刊文献+

可适应线路结构动态变化的有源消弧算法 被引量:44

An Active Arc-Suppression Algorithm Adaptable to Dynamic Structure Variation of Transmission Line
原文传递
导出
摘要 小电流接地故障发生后,为使有源消弧法在配电网线路可能发生切换的情况下仍具有良好的消弧性能,提出了能适应线路结构动态变化的有源消弧算法。故障发生后,注入电流并测量母线零序电压,计算接地电阻。在接地电阻较大时,忽略线路压降,控制故障相电压为0,即采用电压消弧法;在接地电阻较小时,利用配电网自动化装置计算故障后配电网零序导纳,控制故障点电流为0,即采用电流消弧法。仿真结果验证了所提算法的有效性。 To make active arc-suppression method still remaining satisfied arc-suppression performance under possible switching over of distribution line after the occurrence of small current earth fault, an active arc-suppression algorithm adaptable to the dynamic structure variation of transmission line is proposed. After the occurrence of small current earth fault, injecting current, through injecting current and measuring zero-sequence voltage of the bus the grounding resistance can be calculated. For higher grounding resistance, neglecting voltage drop on transmission line the current in the fault phase is controlled to be zero, it means to adopt the voltage-based arc-suppression method; for lower grounding resistance, the distribution automation device is utilized to calculate the post-fault zero-sequence admittance of distribution network and the current at the fault position is controlled to be zero, namely the current-based arc-suppression method is adopted. The correctness of the proposed method is validated by simulation results.
出处 《电网技术》 EI CSCD 北大核心 2014年第7期2008-2013,共6页 Power System Technology
基金 国家自然科学基金资助项目(51077090) 国家863高技术基金项目(2012AA050213) 国家电网公司科技项目(JS031[2012]19)~~
关键词 小电流接地故障 有源消弧法 故障相电压 电压消弧 故障点电流 电流消弧 small current earth fault active arc-suppression method fault phase voltage voltage-based arc-suppression fault current current-based arc-suppression
  • 相关文献

参考文献12

二级参考文献92

共引文献440

同被引文献366

引证文献44

二级引证文献302

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部