摘要 以保定市某建筑为例对其中央空调系统的能耗进行分析。结合其室内功能和热湿环境,提出采用低温送风及变风量空调技术对现有空调系统进行改造的方案,并分析低温送风空调系统和变风量技术的特点,通过比较常温定风量空调系统、低温定风量空调系统、常温变风量空调系统和低温变风量空调系统的系统总能耗及其主要的设备能耗,得出低温变风量空调系统的能耗最低,有明显的节能效果。采用低温送风技术,空调系统能节能23%。采用低温送风和变风量技术,相对常温定风量系统,节能率可达到43%左右。 With the help of an existing building, the energy consumption of HVAC system was analyzed, and the energy consumption proportion of the fans and chillers were calculated in this paper. Considering the building function and thermal environ- ment, the cold air distribution combined with the variable air volume (VAV) system was introduced to reduce the energy consumption of HVAC system, and the corresponding characteristics were analyzed. By comparing with the system energy consumption of the conventional constant air volume (CAV) system, cold air distribution CAV system, conventional VAV system, and the cold air distribution VAV system, the results were concluded that energy consumptiond of the cold air distribution VAV system is the lowest one, it has obvious energy saving effect, the energy consumption ratio is up to 43%.
作者 李蕾 魏兵
出处 《低温与超导》 CAS 北大核心 2014年第9期64-68,共5页 Cryogenics and Superconductivity
关键词 低温送风 常温送风 变风量 能耗 节能 Cold air distribution, Conventional air conditioning system, Variable air volume (VAV), Energy consumption,Energy savings
  • 相关文献

参考文献8

二级参考文献29

共引文献60

同被引文献49

  • 1黄玉珠.超高层建筑给水方式的能耗计算[J].建筑节能,2020(5):106-110. 被引量:3
  • 2王道高,程钧谟.折旧对项目评价指标影响的比较分析[J].山东理工大学学报(自然科学版),2004,18(3):66-69. 被引量:2
  • 3LI X W, ZHANG X S, SHUO Q. Evaporative supercooling method for ice production [J].Applied Thermal Engineering, 2012, 37(1): 120-128.
  • 4邹杰.一种动态冰蓄冷设备:200720058204.6[P].2008—10—1.
  • 5邹杰.一种蓄冷设备:201310047656.4[P].2013—05-09.
  • 6ZHOU X L, LI N P. Research on Energy-saving of new type low-temperature air flow dehumidification system based on exergy analysis method [C]// Proceedings of ISHVAC-COBEE conference, Tianjin, July 12-15, 2015.
  • 7HURDOGAN E, BUYUKALACA O, HEPBASLI A. Exergetic modeling and experimental performance assessment of a novel desiccant cooling system [J].Energy and Buildings, 2011,43(6) : 1489-1498.
  • 8AHMADI P, DINCER I. Thermodynamic and exergoenvironmental analyses, and multi-objective optimization of a gas turbine power plant[J].Applied Thermal Engineering, 2011, 32(14/15): 2529-2540.
  • 9BAI.TA M T, DINCER I, HEPBASLI A. Exergoeconomic analysis of a hybrid copper-chlorine cycle driven by geothermal energy for hydrogen production [J].International Journal of Hydrogen Energy, 2011, 36(17): 11300-11308.
  • 10CHEN L G, FENG H J, SUN F R. Exergoeconomic performance optimization for a combined cooling, heating and power generation plant with an endoreversible closed Brayton cycle [J]. Mathematical and Computer Modeling, 2011, 54 ( 11/12 ) : 2785-2801.

引证文献5

二级引证文献15

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部