摘要
通过对干燥地区的新疆巴楚棉纺公司办公楼及昌吉五彩湾电厂办公楼这些民用建筑中应用三级组合式蒸发冷却空调机组进行调研和现场测试分析,其测试结果表明:三级组合式蒸发冷却空调机组将室外干球温度为33.7℃,湿球温度为19.6℃(巴楚)和室外干球温度为35℃,湿球温度为19.8℃(昌吉)的空气,处理至低于各室外空气的湿球温度甚至接近各室外空气对应的露点温度,然后将这样的低温空气送入室内,完全可以满足民用建筑人体热舒适要求。同时针对实际存在的问题提出相关解决方案,为完善和推广三级组合式蒸发冷却空调技术在民用建筑中的应用提供经验借鉴。
This article through to the dry areas of Xinjiang Bachu cotton company office building and Xinjiang Changji Wucaiwan power plant building these civil building tertiary combined evaporative cooling air conditioning unit in the research and the analysis of field test, the test results have showed that triple modular evaporative cooling air conditioning units will be outdoor dry bulb temperature of 33.7℃, wet bulb temperature of 19.6℃(Bachu) and outdoor dry bulb temperature of 35℃, wet bulb temperature of 19.8℃(Changji) air, handle to below the outdoor air wet bulb temperature even close to the corresponding outdoor air dew point temperature, then the low temperature air into the indoor, can satisfy completely the requirements of civil construction of human body thermal comfort. At the same time puts forward corresponding solutions, aiming at the problems actually to improve and promote tertiary combined evaporative cooling air conditioning technology in the application of civil building to provide experience for reference.
出处
《洁净与空调技术》
2014年第3期88-92,共5页
Contamination Control & Air-Conditioning Technology
关键词
三级组合式蒸发冷却空调
管式间接蒸发冷却器
干球温度
湿球温度
The third-level evaporative air conditioning
Tube type indirect evaporative cooler
Dry-bulb temperature
Wet-bulb temperature