期刊文献+

三级组合式蒸发冷却空调机组在办公楼中的应用分析 被引量:1

The Analysis of Application in the Building That the Third-Level Evaporative Cooling Air Conditioning Units
下载PDF
导出
摘要 通过对干燥地区的新疆巴楚棉纺公司办公楼及昌吉五彩湾电厂办公楼这些民用建筑中应用三级组合式蒸发冷却空调机组进行调研和现场测试分析,其测试结果表明:三级组合式蒸发冷却空调机组将室外干球温度为33.7℃,湿球温度为19.6℃(巴楚)和室外干球温度为35℃,湿球温度为19.8℃(昌吉)的空气,处理至低于各室外空气的湿球温度甚至接近各室外空气对应的露点温度,然后将这样的低温空气送入室内,完全可以满足民用建筑人体热舒适要求。同时针对实际存在的问题提出相关解决方案,为完善和推广三级组合式蒸发冷却空调技术在民用建筑中的应用提供经验借鉴。 This article through to the dry areas of Xinjiang Bachu cotton company office building and Xinjiang Changji Wucaiwan power plant building these civil building tertiary combined evaporative cooling air conditioning unit in the research and the analysis of field test, the test results have showed that triple modular evaporative cooling air conditioning units will be outdoor dry bulb temperature of 33.7℃, wet bulb temperature of 19.6℃(Bachu) and outdoor dry bulb temperature of 35℃, wet bulb temperature of 19.8℃(Changji) air, handle to below the outdoor air wet bulb temperature even close to the corresponding outdoor air dew point temperature, then the low temperature air into the indoor, can satisfy completely the requirements of civil construction of human body thermal comfort. At the same time puts forward corresponding solutions, aiming at the problems actually to improve and promote tertiary combined evaporative cooling air conditioning technology in the application of civil building to provide experience for reference.
出处 《洁净与空调技术》 2014年第3期88-92,共5页 Contamination Control & Air-Conditioning Technology
关键词 三级组合式蒸发冷却空调 管式间接蒸发冷却器 干球温度 湿球温度 The third-level evaporative air conditioning Tube type indirect evaporative cooler Dry-bulb temperature Wet-bulb temperature
  • 相关文献

参考文献11

二级参考文献48

共引文献101

同被引文献14

引证文献1

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部