摘要
统计分析广州蓄能水电厂B厂静止变频器自然换相阶段过流故障现象及原因。基于实测及理论推断,指出其缺陷在于静止变频器逆变器逆变角β裕度不足。通过改进静止变频器的逆变角β,消除了过流故障模式。
The over-current faults in commutation process of Static Frequency Convertor (SFC) in the Plant B of Guangzhou Pumped Storage Power Station and its reasons are analyzed based on the statistical operation data. Based on measured data and theoretical analyses, the over-current faults are mainly caused by insufficient margin of inverter inverting angle β. The over-current faults are finally eliminated by adding the inverting angle β of SFC.
出处
《水力发电》
北大核心
2014年第11期4-5,54,共3页
Water Power
关键词
静止变频器
自然换相
过流
逆变角
广州蓄能水电厂
Static Frequency Convertor(SFC)
natural commutation
over-current
inverting angle
Guangzhou Pumped StoragePower Station