期刊文献+

闭式高压细水雾灭墙角火的试验研究

Experimental Study of Closed High Pressure Water Mist System in Extinguishing Corner Fire
下载PDF
导出
摘要 为了掌握闭式细水雾灭墙角火的规律,在不同流量特性k系数、压力、喷射角状况下进行了多次灭火试验,研制了一种细水雾喷头。经过春、秋及梅雨季不同温度、湿度状况下二十多次灭火试验,总结了南方梅雨期湿度增大对室内墙角火灭火试验的影响和规律。结果表明,影响细水雾灭墙角火的重要因素之一是环境湿度。细水雾喷头采用相同温度等级的玻璃球(57℃)可以降低(或消除)环境湿度的影响。细水雾喷头喷雾压力推荐使用范围为10~12 MPa。对闭式细水雾室内墙角火工程设计具有参考作用。 In order to understand the laws of the extinguishing corner fire of closed water mist system through, a series of experi-ments which are conducted under K coefficient, pressure, and nozzle spray angle of different flow, this paper develops a new noz-zle. Its extinguishing tests are conducted under the condifions of the different temperature and humidity in spring. autumn and mould-rains season. The results demonstrate that environment humidity has great impact on the result of the extinguishing corner fire. If the nozzles are equipped with the glass bal of the same temperature rating ( 57℃) , the effect of the humidity is minimized and elimina-ted. It is best to control the water mist nozzle pressure within the range of 10~12 MPa. This paper provides the valuable reference for engineering design of closed water mist system for extinguishing corner fire.
作者 韩建
出处 《机械制造与自动化》 2014年第6期229-235,共7页 Machine Building & Automation
关键词 闭式细水雾喷头 热敏玻璃球 消防 灭火试验 室内墙角火 closed water mist nozzle nozzle thermo-sensitive component fire extinguishing extinguishing test comer fire
  • 相关文献

参考文献8

二级参考文献14

共引文献8

相关作者

内容加载中请稍等...