期刊文献+

一起35 kV干式空心电抗器故障分析 被引量:16

Fault Analysis of 35 kV Dry-type Air Core Reactor
下载PDF
导出
摘要 结合干式空心电抗器的绝缘材质、运行环境及运行方式的瞬变,对一起35 kV干式空心电抗器故障原因进行分析,发现导致故障发生的主要原因是电抗器的绝缘材质耐热等级低和电容器组的频繁投切导致绕组局部匝间绝缘击穿,造成电流急剧增大,大电流产生高温诱使绕组绝缘相对薄弱处发生匝间短路。并针对性提出故障防范措施,为电抗器的安全运行提供保障。 In this paper,the fault of 35 kV dry type air core reactor is analyzed based on the combination of insulation material,service environment and transients of operation mode. It is found that the main reason of the fault is the low thermal withstand level of insulation material and the frequent switching of capacitor bank,leading to insulation breakdown between partial turns of winding and significant increase of current. The high temperature due to high current induces inter-turn short circuit of winding at relative weak insulation place. The precautionary measures are proposed which provide assurance for safe operation of reactor.
出处 《电力电容器与无功补偿》 2014年第5期92-95,共4页 Power Capacitor & Reactive Power Compensation
关键词 干式空心电抗器 匝间短路 故障分析 防范措施 dry-type air core reactor inter-turn short circuit fault analysis preventive measures
  • 相关文献