期刊文献+

一起燃机启动电动机电流速断跳闸的分析及处理

Analysis and Processing of an Accident of Instantaneous Current Trip in a Gas Turbine Start Motor
下载PDF
导出
摘要 结合一起电动机电流速断保护频动事故,对事故发生的原因从电气和机械特性方面进行了详细分析,并结合电动机的实际运行情况进行了故障处理,最终判定跳闸主要是由电动机启动瞬间的电流衰减时间较空载时间长引起的。通过调整定值,启动电动机出现电流速断保护动作跳闸的问题得到解决。 This paper analyzes a motor current instantaneous protection frequency trip acci- dent. The cause of the accident is studied in detail from the electrical and mechanical characteris- tics. The fault is dealt with according to the actual operation of the motor. It is determined that the main reason of tripping that, when the motor starts, the instant current decay time is longer than that without load. By adjust the setting values, the problem of start motor current instanta- neous trip protection is resolved.
作者 王成平
出处 《上海电机学院学报》 2015年第1期58-62,共5页 Journal of Shanghai Dianji University
关键词 燃气轮机 启动电动机 电流速断保护 故障处理 gas turbine start motor current instantaneous trip protection fault treatment
  • 相关文献

参考文献14

二级参考文献18

  • 1刘尚明,王纯.燃气轮机及联合循环一次调频控制综述[J].热力透平,2004,33(3):154-157. 被引量:21
  • 2石飞,林莘,徐建源.真空断路器弹簧操动机构的机械特性与可靠性[J].电力设备,2005,6(6):79-81. 被引量:9
  • 3Siemens AG. Shanghai Huaeng Power International,inc Shidongkou Combined Cycle Project (CHN766- YFE -4181 -400101 ). 2005.
  • 4中国华北电力集团公司.京津唐电网自动发电控制(AGC)运行管理办法(试行)[S].2002.
  • 5中国华北电力集团公司.华北电网发电机组一次调频运行管理规定(试行)[S].2003.
  • 6刘介才.工厂供电(第3版)[M].北京:机械工业出版社.2000.
  • 7罗钰铃,吕铁民,陈家媚,等.电力系统微机继电保护[M].北京:北京人民邮电出版社,2005.
  • 8胡人亮.苔藓植物学[M]高等教育出版社,1987.
  • 9中国科学院青藏高原综合科学考察队.西藏苔藓植物志[M]科学出版社,1985.
  • 10吴鹏程等.苔藓名词及名称[M]科学出版社,1984.