工业用冷却塔不同填料的性能对比 被引量:4

Performance Comparison of Industrial Cooling Tower Different Fillers
下载PDF
导出
摘要 利用麦克尔方程和辛普逊积分法,对工业冷却塔常用的S波、人字波、复合波三种波形的填料性能进行了实验研究,结果显示:在淋水密度为8 t /(m2·h)时,复合波型填料热学性能较其它两者要好,其蒸发特性数是人字波型的1.081~.34倍,是S波型的1.06~1.1倍,在满足相同冷却负荷要求下,选用复合波填料的最佳气水比相对较小,对应的迎面风速也最低,可为实际应用提供指导。 Based on Meckel equation and Simpson integral method, experiments were carried out to test cooling tower fillers performance, which were made of s wave, herringbone wave and composite wave form. The result showed that composite wave filler was better that others when pouring water density was 8 t /(m2·h), whose evaporation characteristics is about 1.081 ~ .34 times of herringbone’s, whose evaporation characteristics is about 1.06 ~ 1.1 times of s wave’s. Under the situation of meeting same cooling load, composite wave filler’s optimal gas-water ratio is small and face velocity is low, which could provide reference for practical application.
出处 《上海节能》 2015年第6期324-329,共6页 Shanghai Energy Saving
关键词 工业用冷却塔淋水填料 热学性能 蒸发特性数 最佳气水比 Industrial Cooling Tower Thermal Performance Evaporation Coefficient Optimal Gas-Water Ratio
  • 相关文献

参考文献8

二级参考文献15

  • 1由世俊,张卫江.金属填料型直接蒸发式空气冷却器的研究[J].制冷学报,1994,16(4):28-31. 被引量:17
  • 2张庆民,陈沛霖.空气经过淋水纸质填料时的热湿交换过程[J].同济大学学报(自然科学版),1995,23(6):648-653. 被引量:24
  • 3-.电子计算机算法手册[M].上海:上海教育出版社,1982..
  • 4黄翔 等.两种适合西北地区气象条件的新型空调设备的[M].,1999(1)..
  • 5宣永梅 等.直接蒸发冷却与喷水室的对比分析[J].纺织空调除尘,1999,(3).
  • 6严煦世,给水工程,1995年
  • 7秦萧,冶金动力,1993年,5期,21页
  • 8许保玖,给水处理,1979年
  • 9赵振国,冷却塔,1997年
  • 10电子计算机算法手册,1982年