期刊文献+

风电场无功补偿装置选型研究 被引量:10

Study on Selection of Reactive Power Compensation Device for Wind Farm
下载PDF
导出
摘要 由于初始投资方面的优势,风电场无功补偿装置的型式一般为SVG+FC,全SVG型式应用较少。借助风速威布尔分布建立无功补偿装置损耗计算模型,对无功补偿装置型式的优化设置进行分析,同时对SVG+FC和全SVG两种型式进行初始投资和运行损耗方面的比较,供风电场设计相关同行及有关研究部门参考。 The type of reactive power compensation device for the wind farm, due to the advantage of initial investment,is generally SVG+FC and the application of total SVG type is less. The loss calculation model of the reactive power compensation device is set up with the help of wind velocity Weibull distri- bution and the optimization setting of the reactive power compensation device is analyzed and, at the same time, the comparison of SVG+FC and SVG in the initial investment and operation loss is supplied to those who are involving the design of wind farm and related research authorities for reference.
机构地区 中南电力设计院
出处 《电力电容器与无功补偿》 北大核心 2015年第4期27-31,共5页 Power Capacitor & Reactive Power Compensation
关键词 风电场 无功补偿装置 威布尔分布 wind farm reactive power compensation device Weibull distribution
  • 相关文献

参考文献13

二级参考文献91

共引文献156

同被引文献77

引证文献10

二级引证文献50

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部