摘要
基于对厂用电系统继电保护中存在的配置不完整、后备保护动作时间过长等问题的分析,提出了配置6kV母线专用主保护、在低压厂用电系统变压器高压侧增加限时电流速断保护装置、优化后备保护之间配合的方案,并以此对厂用电系统的继电保护配置进行了优化,以600 MW机组为例,进行了保护整定计算,结果表明,优化后的厂用电系统继电保护配置完整,保护范围合理,后备保护动作时间显著缩短。从而,提高了厂用电系统继电保护动作的快速性和厂用电系统运行安全性。
On the basis of analysis on some questions of relay protection in auxiliary power systems,like the imperfection in configuration and the actuation time is too long,a scheme was proposed for relay protection design,such as configuring a specialized main protection for 6 kV busbar,adding a time limited current fast-trip protection on the high-voltage side of low-voltage transformers in auxiliary power system,optimizing the cooperation of reserve protections and then designing the configuration of relay protection in auxiliary power system according to the optimizing rule.Taking a 600 MW unit as the example,settings calculation was carried out.The results proved that the configuration of relay protection in auxiliary power system is integrated perfectly due to the optimization,the coverage of protection is reasonable and the actuation time of reserve protection has been remarkably shortened.Thus,the actuation speed and security of the auxiliary power system are promoted.
出处
《热力发电》
CAS
北大核心
2015年第9期113-116,共4页
Thermal Power Generation
关键词
厂用电系统
继电保护
配置
专用主保护
后备保护
动作时间
整定计算
auxiliary power system
relay protection
configuration
specialized main protection
reserve pro-tection
actuation time
settings calculation