数据机房冷通道应用的气流模拟及热性能分析 被引量:7

Analysis of CFD Simulation and Thermal Performance for Cold Aisle Enclosure Application in Data Center
下载PDF
导出
摘要 以简化的数据机房为对象,对冷通道封闭前后的热环境进行计算流体力学模拟,采用供热指数SHI和气流分布系数RTI两个热环境评价指标,分析送风口与服务器之间以及送回风口之间冷量损失比例。模拟结果表明,冷通道封闭及未封闭的RTI指标分别为1.0、0.50~0.85,未封闭SHI指标表明有热气流掺混;冷通道封闭能最大限度地将冷空气封闭在冷通道内,有效地提高了冷量利用效率。 Based on a object of simplified data center, this paper simulated the thermal environment with and without the cold aisle enclosure by computational fluid dynamics (CFD) software. Two evaluation indexes of supply heating index(SHI) and return temperature index (RTI), are used to evaluate the loss ratio of the cooling capacity between supply-air inlets and servers, supply-air inlets and return-air outlets. The simulation results show that the RTI with and without the cold aisle enclosure is 1 and 0.50 - 0.85, respectively. The SHI without the cold aisle enclosure indicates the hot air mixing exists. The cold aisle enclosure can ensure the cold air into the cold aisle as much as possible,which improves the utilization efficiency of cooling capacity.
出处 《现代建筑电气》 2015年第9期1-5,17,共6页 Modern Architecture Electric
基金 国家国际合作项目(2015DFA61170) 湖南省重点项目(2013WK2001)
关键词 数据中心 冷通道封闭 计算流体力学 SHI RTI data center cold aisle enclosure computational fluid dynamics(CFD) SHI RTI
  • 相关文献

参考文献6

二级参考文献15

  • 1中国电子工程设计院.GB50174-2008电子信息系统机房设计规范[S].北京:中国计划出版社,2009.
  • 2云计算发展与政策论坛.数据中心能效测评指南[C].2012.
  • 3Environmental Protection Agency. Report to congress on server and data center energy efficiency [-R. Public Law 109-431. U S, 2007.
  • 4Sun H S, Lee S E. Case study of data centers' energy performance[J. Energy and Buildings, 2006,38 (5) . 522-533.
  • 5Koomy J G. Growth in data center electricity use 2005 to 2010 EEB/OL. E2011 http: /// www. analyticspress, eom/datacenters, html.
  • 6ASHRAE. ASHRAE TC 9.9 Thermal guidelines for data processing environments expanded data center classes and usage guidanceES, 2011.
  • 7Sharma R K, Bash C E, Patel R D. I)imensionless parameters for evaluation of thermal design and performance of large-scale data centersC// In 8th ASME/AIAA Joint Thermophysies and Heat Transfer Conference, 2002.
  • 8Herrlin M. Rack cooling effectiveness in data centers and teleeom central offices the rack cooling index (RCI)EGT// ASHRAE Trans, 2005,111(2) : 1 -11.
  • 9Cho J, Kim B S. Evaluation of air management system's thermal performance for superior cooling efficiency in high-density data centers[J. Energy and Buildings, 2011,43(9). 2145-2155.
  • 10BEITELMAL M H,PATEL C D. Thermo-Fluids Provisioning of a High Performance High Density Data Center[D].HP Laboratories Palo Alto,2004.

共引文献75

同被引文献24

引证文献7

二级引证文献14

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部