期刊文献+

结合DFIG功率特性研究风电并网对系统功角稳定性的影响 被引量:21

Research on Influence of Integrated Wind Plants on Power Angle Stability Based on Output Characteristic of DFIG
原文传递
导出
摘要 大容量风电并网条件下的系统功角稳定特性对于新能源送出与消纳具有重要意义。基于双馈风力发电机组的运行与控制原理分析了其出力特性,指出双馈机组在暂态稳定分析中可近似看做恒功率源;结合实测曲线,说明恒功率源模型较实际情况更具保守性。以并列运行同步机组故障清除后输出电磁功率为指标,研究送端电网风火互替对于系统功角稳定水平的影响,提出双馈风电等量替代同步电源将改善功角稳定水平,并从系统能量平衡角度进一步探讨了其内在原理与适用范围。最后,通过单机?无穷大系统、两机系统和哈密风火打捆送出系统算例仿真验证了上述结论。 System power angle stability characteristics under condition of large amount of integrated wind power are important for new energy delivery and accommodation. Based on analysis of output characteristics and control principle of doubly-fed inductor generators(DFIG), the issue that DFIG could be treated as constant power resource in transient analysis is presented. Conservative feature of constant power resource model is demonstrated by comparing with measured curve of DFIG. Effect of replacing thermal power with DFIG in sending end on power system stability is studied with index of parallel operating synchronous generator' electromagnetic power at moment of fault clearance, and further analysis of inherent principle of energy balance is performed. Correctness is verified with simulation results of example cases including single machine infinite bus power system, two-region power system and Hami grid.
出处 《电网技术》 EI CSCD 北大核心 2015年第12期3401-3407,共7页 Power System Technology
关键词 双馈风电机组 功率特性 风火互替 功角稳定 doubly-fed inductor generators power characteristics replacement of synchronous generator with DFIG power angle stability
  • 相关文献

参考文献21

二级参考文献182

共引文献1050

同被引文献224

引证文献21

二级引证文献139

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部