期刊文献+

排烟口与送风口关系对送风排烟的影响 被引量:7

The influence of relationship of smoke exhaust vent and air outlet on air supply and smoke exhaust system
下载PDF
导出
摘要 为探求合适的排烟口与送风口的尺寸关系,通过理论分析,推导出影响正压送风排烟效果的通风因子,该通风因子同排烟口与送风口的面积比成正相关关系,进行了全尺寸试验。结果表明,排烟口与送风口面积比为2∶1时可以达到较好的排烟效果。研究结果可为正压送风排烟在火场中的实战应用提供一定的理论与技术指导。 In order to find proper proportion of smoke exhaust vent to air outlet, by theoretical analysis, derive ventilation fac- tor influencing effect of air supply and smoke exhaust, and the ventilation factor is positive correlated with proportion of smoke exhaust vent to air outlet, then full-scale experiment is carried out, and the results show that when the proportion of smoke ex- haust vent to air outlet is 2 : 1 ,the smoke exhaust effect is the best. the results can give theoretical and technical guide for ap- plication of positive air supply system in fire.
出处 《消防科学与技术》 CAS 北大核心 2015年第12期1597-1600,共4页 Fire Science and Technology
基金 公安部消防局重点攻关项目(2014XFGG02)
关键词 排烟方式 正压送风排烟 通风因子 排烟口 smoke exhaust method positive air supply and smoke exhaust system ventilation factor smoke exhaust vent
  • 相关文献

参考文献8

  • 1霍然,胡源,李元洲.建筑火灾安全工程导论(第二版)[M].合肥:中国科学技术大学出版社,2009.
  • 2郭铁男.中国消防手册·第十卷·火灾扑救[M].上海:上海科学技术出版社.2006.
  • 3Stott R. Report on PPV trials at Oxford road[R]. 2000.
  • 4Svensson S. ExPerimental study of fire ventilation during fire fight ing operadons[J]. Fire Technology( s 0015 - 2684), 2001,37 : 69-85.
  • 5Lcmgheed G D, Mcbride P J, Carpenter D W. Positive pressure ventilation for high rise buildings[R]. Canada: Research report National Researcl Svensson, S. Fire ventialation[M]. Sweden:NRS Tryckeri, Huk varna, 2000.
  • 6Svensson, S. Fire ventialation[M]. Sweden:NRS Tryckeri, Huk- varna, 2000.
  • 7苏琳.移动式排烟机安放位置的讨论[J].消防科学与技术,2012,31(1):29-32. 被引量:12
  • 8李思成,荀迪涛,王万通.正压送风排烟在火场中的应用[J].消防科学与技术,2013,32(9):1023-1026. 被引量:23