PT断线后电抗器匝间保护新判据 被引量:9

New Criterion on Shunt Reactor Inter-turn Protection When PT Secondary Circuit Open
原文传递
导出
摘要 电抗器在电压互感器(potential transformer,PT)断线后均采取闭锁匝间保护的策略,容易造成故障范围的扩大。该文分析电抗器PT断线时零序阻抗计算的方法,研究电抗器区外故障和匝间故障时首末端故障电流的特点;在此基础上提出基于零序阻抗和故障电流特征的PT断线后电抗器匝间保护新判据,并在PSCAD/EMTDC电磁暂态仿真平台上验证理论分析的正确性。该判据完善了现有电抗器保护方法。最后在动模实验室建立线路电抗器系统模型,动模仿真结果验证了理论分析计算的正确性。 The strategy of blocking inter-turn protection is adopted when potential transformer(PT) secondary circuit is open, but it can expand the failure range easily. This paper analyzed the calculation method of zero sequence impedance when reactor PT secondary circuit open, characteristics of initial and terminal current was studied after inter-turn fault and external fault at the reactor, new criterion about shunt reactor inter-turn protection when PT secondary circuit open was proposed on the basis of zero sequence impedance and fault current characteristic, the correctness of the theoretical analysis was verified in PSCAD/EMTDC electromagnetic transient simulation platform, this criterion improves the existing reactor protection methods. Reactor and line system model was established in the dynamic simulation lab, dynamic simulations results verified the validity of the theoretical analysis and calculation.
出处 《中国电机工程学报》 EI CSCD 北大核心 2015年第24期6398-6404,共7页 Proceedings of the CSEE
关键词 电压互感器断线 零序阻抗 继电保护 新判据 potential transformer(PT) secondary circuit open zero sequence impedance relay protection new criterion