期刊文献+

变温环境室室内热环境实验研究

Experimental study on indoor thermal environment of variable temperature ambient chamber
原文传递
导出
摘要 通过设计计算得出送风道的送风速度和环境室的气流分布,并与实验进行对比。实验结果表明,4个送风口的风量分配比较均匀,与均匀送风道设计风速和环境室气流组织计算风速3.57m/s相吻合;采用均匀送风道送风和单风口回风的方式,能够实现较好的气流组织和温度场,室内空气温度波动基本在1℃以下,但是在低温工况下上部空气波动幅度较大;相对湿度随环境室温度工况的升高,先升高后降低,在12℃工况下出现最大值。 This paper drawn air velocity of air channel and air distribution of environmental chamber through the design and calculation . And by experimental verification design was reasonable. The results showed that air distribution of the four outlet are relatively uniform . And uniform air flow channel designed wind speed and ambient room air distribution calculated wind speed 3. 57m / s coincide. The way of uniform air channels supplying air and single outlet returning air can achieve better air distribution and temperature field. The fluctuations of indoor air temperature is substantially 1 ℃ or less. The upper air temperature in the low temperature conditions is greater volatility. Relative humidity increases with ambient room temperature conditions, reduces after the first increase,and a maximum value at 12 ℃ conditions.
出处 《低温与超导》 CAS 北大核心 2016年第1期70-74,共5页 Cryogenics and Superconductivity
关键词 变温环境室 送回风速度 温度场 湿度 Variable temperature ambient chamber, Back to the air velocity, Temperature field, Humidity
  • 相关文献

参考文献6

二级参考文献10

  • 1陆亚俊.制冷技术及其应用[M].北京:中国建筑工业出版社,1994..
  • 2杨善勤,编著.民用建筑节能设计手册.北京:中国建筑工业出版社,1998
  • 3华北地区建筑设计标准化办公室.91SB6(通风与空调工程)建筑设备安装通用图集
  • 4陆亚俊,制冷技术及其应用,1994年
  • 5浙江省丽水地区教委教研室,食用菌生产,1993年
  • 6陆亚俊,暖通空调,1991年,21卷,1期
  • 7GBJ19-87.采暖通风与空气调节设计规范.[S].,..
  • 8殷平.常规空调大温差技术探讨[J].暖通空调新技术,2000,.
  • 9Allan T.Kirkpatirck and James S.Elleson.COLD.AIR DISTRIBUTION SYSTEM DESING GUIDE.1996[M].
  • 10陆亚俊,马最良.10—15℃低温空调系统设计[J].施工技术,1991,20(1):35-37. 被引量:1