期刊文献+

互感引起的零序方向保护误动分析与对策 被引量:1

Analysis and Countermeasures on a Malfunction of Zero-Sequence Directional Protection Due to Mutual Inductance
下载PDF
导出
摘要 粜220kV线路高频零序方向保护在区外故障时误动,保护动作前的电压波形存在明显畸变。通过对电瓜波形进行谐波分析,发现电容式电压互感器(CVT)暂态特性持续时间比较短,一般在5~10ms.而零厅办向保护动作m口在20ms以后,从而排除了CVT暂态特性不良引起零序方向保护误动的可能性。同时小槲线路心侧岑序电压、零序电流及零序阻抗,计算出线路上存在感应电压.从而确认相邻线路互感是导致零序方向保护误判的原因,并有针对性地提出负序电流开放零序方向保护的改进措施。 A high frequency zero-sequence directional protection of a 220 kV line took false action with obvious distortion on voltage waveform. Through harmonic analysis of voltage waveform, it is found that CVT transient characteristics lasted shortly around 5 -10 ms, while zero-sequence directional protection acted 20 ms later. The possibility of malfunction caused by transient characteristics of CVT is excluded. Based on zero-sequence voltage, current and sequence on both sides of protection, the induced voltage is calculated. It is inferred that mutual inductance is the cause of malfunction of zero-sequence directional protection. A new zero-sequence directional protection scheme with negative sequence current opening identification is proposed.
出处 《中国电力》 CSCD 北大核心 2016年第5期59-62,共4页 Electric Power
关键词 零序方向保护 暂态特性 CVT 互感 zero-sequenced directional protection transient characteristics CVT mutual inductance
  • 相关文献

参考文献10

二级参考文献73

共引文献112

同被引文献8

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部