期刊文献+

1000MW机组凝汽器水侧流场的三维数值模拟 被引量:5

3D Simulation on Flow Field at Condenser Water Side of a 1000 MW Unit
下载PDF
导出
摘要 以某1 000MW机组为例,利用Fluent软件对凝汽器水侧的流场特性进行了数值模拟.结果表明:循环水在高压凝汽器和低压凝汽器前水室产生的较大漩涡区和循环水对管板的冲击,增加了循环水的阻力损失,影响了管束区水速的分布;在进口水室加装导流板和隔板上加装凸起扣板后,水室内的漩涡区明显减小,水速变得均匀平顺,循环水对隔板冲击现象明显减弱,且沿着凸起扣板方向进入管束,管束区平均水速提高了0.033m/s,整体平均传热系数增大了28 W/(m^2·K),改善了凝汽器水侧管束的传热效果. Taking a 1 000 MW unit as an example, numerical simulations were conducted on flow characteristics at its condenser water side using Fluent software. Results show that the large vortex produced by circulating water in the water chamber of high- and low-pressure condenser and the impact of circulating water on the tube plate would lead to the increase of resistance loss and the non-uniform distribution of water velocity in tube bundle areas; the phenomenon of water swirl can be significantly reduced by adding guiding plates and convex buckles in the water chamber, where the water velocity would become uniform and smooth, the impingement on baffle plate would be weakened, and the water would flow into the tube bundle along the direction of convex buckles, resulting in increased average water velocity by 0. 033 m/s and raised overall heat-transfer coefficient by 28 W/(m2· K), indicating obvious improvement of heattransfer effect at water side of the condensers.
作者 周兰欣 张娜
出处 《动力工程学报》 CAS CSCD 北大核心 2016年第7期525-529,550,共6页 Journal of Chinese Society of Power Engineering
关键词 凝汽器 水室 管柬 传热系数 导流板 凸起扣板 condenser water chamber tube bundle heat-transfer coefficient guiding plate convex buckle
  • 相关文献

参考文献7

二级参考文献74

共引文献81

同被引文献33

引证文献5

二级引证文献7

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部