摘要
通过对清江水布垭电厂主变压器高压套管介损值历年数据及套管材料结构的分析,证实环氧浸纸型套管介损值也是不必进行温度换算的,它对水电厂相关规程的修订,提供了有参考价值的机组运行数据。
An analysis is carried out on the dielectric loss data over the years and the material of the high voltage bushing in the main transformer in Shuibuya Hydropower Plant. It shows that the temperature conversion is unnecessary for the dielectric loss analysis of oil impregnated paper insulation bushing. These operation data could be useful references for the revision of related regulations.
出处
《水电与新能源》
2016年第11期31-32,共2页
Hydropower and New Energy
关键词
浸纸绝缘型套管
温度
介损值
套管材料
oil impregnated paper insulation bushing
temperature
dielectric loss value
bushing material