期刊文献+

双层内衬改造技术在埋地油罐中的应用研究 被引量:3

Application Research of Double Wall Lining Reform Technology in Underground Storage Tank
下载PDF
导出
摘要 介绍了共结构双层内衬改造技术,其结构共由5层组成,分别为基础层(防腐层和加强密封层组成)、中空监测层、内衬加强层、防油防腐层和导静电层;采用该技术可对加油站埋地单层钢制油罐进行双层改造,经过罐内清洗、喷砂除锈、基础层施工、中空监测层施工、内衬加强层施工、防油防腐层施工、导静电层施工和整个系统气密性的保压检测,完成双层内衬油罐的现场改造;采用GB30040规定的Ⅰ级真空泄漏监测方法,可以在油品泄漏前报警,实现埋地油罐整体安全水平的提升,具有重要的现实意义。 The research object of this article is a co- structural double wall lining retbrm technology, whose structure is consist of basic layer (anticolTosion layer and strengthening sealing layers) , hollow moni- toring layer, reinforced lining layer, geese proofing layer and electricity conducting layer. Then we use this technology to modify a single wall underground steel storage tank, through tank cleaning, sandblast- ing, building of basic layer, hollow monitoring layer, reinforced lining layer, grease proofing layer, elec- tricity conducting layer and tightness pressure detec- ting of the whole system, the modification of the on- site internal lining double wall tank was succeed. In this paper, we talked about the total structure of the double wall lining reform technology using level I leak detection method in GB30040 -vacuum leak detection that can alarm before the oil spill, which enhance the overall safety level of underground stor- age tank. It is of great practical significance.
出处 《安全、健康和环境》 2017年第7期17-20,共4页 Safety Health & Environment
关键词 内衬法 双层罐 泄漏技术 真空监测 Lining method double layer tank leak- age technology vacuum system monitoring
  • 相关文献

参考文献5

二级参考文献9

  • 1宋生奎,齐永生,彭著良.玻璃钢储油罐在我国加油站中的应用前景[J].化工设备与管道,2006,43(4):25-27. 被引量:4
  • 2斯远.SF油罐从源头把关HSE[J].中国石油石化,2006(16):61-61. 被引量:7
  • 3中国石化工程建设有限公司.汽车加油加气站设计与施工规范[S]北京:中国计划出版社,2006.
  • 4中国石化工程建设有限公司.汽车加油加气站设计与施工规范[S]北京:中国计划出版社.
  • 5袁仁伟;袁君伟;范斌.钢制强化玻璃纤维制双层罐[P]中国,20082003064982008.
  • 6田杰.加油站储油罐渗漏成地下水最大污染源[N].工人日报,2014-03-01(06).
  • 7中华人民共和国建设部.GB50156-2012,汽车加油加气站设计与施工规范[S].北京:中国计划出版社,2012.
  • 8中国兵器工业企业管理协会.AP11631-2001,地下油罐的内衬和定期检验[S].北京:兵器工业出版社,2003.
  • 9Underwriter's Laboratories of Canada.ULC-ORD-C58.4-05, Double Containment Fiber Reinforced Plastic Linings for Flammable and Combustible Storage Tanks[S].Underwriter's Laboratories of Canada,2005.