摘要
以计算流体力学(CFD)为基础,利用PHOENICS软件,对采用孔板风口的地板送风进行数值模拟,分析室内的温度场和速度场,得出孔板风口用于地板送风时送风温度不能低于19℃,送风速度不能高于1m/s。
In this paper, the underfloor air distribution with perforated panels is numerically simulated with PHOENICS software based on computational fluid dynamics (CFD), the temperature field and velocity field are analysis. It is concluded that supply air temperature shall not be lower 19℃and supply air velocity shall not be higher than 1 m/s in underfloor air distribution with perforated panels.
出处
《洁净与空调技术》
2018年第1期1-3,共3页
Contamination Control & Air-Conditioning Technology
关键词
孔板风口
地板送风
温度场
速度场
Perforated panels: Under floor air supply
temperaturefield
Velocity field