国产300 MW火电机组高压加热器给水温升偏低问题分析及改造

Problem Analysis and Reformation for Low Temperature of High Pressure Heater Water Supply of Domestic 300 MW Turbine
下载PDF
导出
摘要 结合某电厂300 MW机组6台高压加热器给水温度低于设计值的异常情况,分析认为分水隔板冲刷、隔板垫片损坏导致的水侧短路是给水温升偏低的主要原因,提出优化分水隔板材质、结构和法兰结构等高压加热器水室分水隔板的改造措施,通过运行情况说明改造效果。 According to the abnormal phenomenons of temperature-rise decreasing of six high pressure heaters of 300 MW turbine in some power plant,this paper proves that the prime reason is short-circuit of water side of high pressure heater through analysis,proposes methods by optimizing the materials and structures of chamber clapboard and manhole flange of high pressure heater,illustrates the effect of revamp by running conditions.
作者 田志强 TIAN ZhiQiang(Matou Cogeneration Branch Company of Datang Hebei Power Generation Co.Ltd.,Handan 056044,China)
出处 《河北电力技术》 2018年第4期40-41,54,共3页 Hebei Electric Power
关键词 高压加热器 给水温升 水侧短路 水室 分水隔板 人孔 high pressure heater temperature-rise of power supply water side short-circuit water chamber clapboard manhole