期刊文献+

钢混复合管片结合处抗剪性能试验研究 被引量:1

Experimental Study on Shear Resistance Cross-section of the Steel-concrete Composite Segment
下载PDF
导出
摘要 通过分析钢混结合面相对位移和结合面处裂缝张开的变化,对该管片钢混结合处力学性能变化及破坏全过程进行研究,并将其分为3个阶段。试验结果表明:钢混结合面的屈服剪力为380kN,极限抗剪承载力为450kN,远大于设计荷载375kN,意味着试验的钢混结合面可满足抗剪设计要求。并通过试验数据拟合得到了3个阶段的抗剪刚度。 By analyzing the changes of the relative displacement and the crack opening of steel-concrete composite surface,the change of mechanical behaviors of the joint structure and the whole process of damage were explored. It was divided into 3 stages. The test results show that the yield shear force of the steel-concrete joint surface is 380 kN, far greater than the design load 250 kN, and the ultimate shear capacity is 450 kN, which means that the steel and concrete joint surface of the test can meet the requirements of shear design. The shear stiffness of the three stage was obtained by fitting the test data.
作者 邓高林 庄欠伟 李东 张弛 DENG Gaoli;ZHUANG Qianwei;LI Dong;ZHANG Chi(Department of Civil Engineering,Shanghai University,Shanghai 200444,China;Shanghai Shield & Research Center Co.,Ltd.,Shanghai 200137,China)
出处 《施工技术》 CAS 2018年第19期42-45,共4页 Construction Technology
关键词 盾构 钢混复合管片 钢混结合面 位移 试验 shields steel-concrete composite segment steel-concrete composite surface displacement testing
  • 相关文献

参考文献8

二级参考文献55

共引文献332

同被引文献4

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部