摘要 为有效降低双回路电缆金属护层的环流,提高电缆的使用寿命和载流量,分析了混合排列方式对双回路交联聚乙烯(XLPE)电缆护层环流的影响。首先,根据电磁学理论,推导了双回路XLPE电缆金属护层环流的计算过程;然后利用自制程序,分析计算了220 kV单芯XLPE电缆采用水平、直角混合排列方式时的护层环流值。研究结果表明:交叉互联分段均匀的情况下,电缆混合排列时的最大环流值将达到负荷电流的14.4%;而400 m-500m-600m分段的情况下,混合排列方式下电缆护层的环流值可达到负荷电流的24.2%,超出了工程允许范围。另外,相同敷设条件下,单回路电缆护层的环流比双回路敷设情况要小30%左右。为抑制XLPE电缆护层的环流,应严格保证交叉互联单元内电缆的排列方式一致,并尽量保证3小段的电缆长度相等。 In order to reduce current in metal sheaths of crosslinked polyethylene(XLPE) cables, and to increase the service life and ampacity of cables, we analyzed the effect of mixed arrangement on current in metal sheaths of two-circuit arranged XLPE cables. Firstly, on the basis of the theory of electromagnetism, a process of calculation of current in metal sheaths of two-circuit arranged XLPE cables was deduced. Secondly, the value of current in sheaths of 220 kV single-core cables, which were laid in both horizontal and right angle form, was calculated by using a self-made program. The research results show that the maximum circulating current value of mixed arranged cables has reached 14.4% of load current when the cables are segmented evenly; under the segmentation of 400 m-500 m-600 m, the current value may be 24.2% of load current which is beyond the allowable range. In addition, the circulating currents in single-circuit cables is about 30% lower than that in double-circuit cables under the same laying conditions. In order to reduce the current in sheaths, we should make sure that the cables, which belong to the cross-bonding unit, should be arranged in the same order, and the length of segments should be equal.
作者 陈科技 齐炜 CHEN Keji;QI Wei(Economic and Technical Research Institute,State Grid Zhejiang Electric Power Company,Hangzhou 310002,China;Zhejiang Electric Power Design Institute Co.,Ltd.,China Energy Engineering Group,Hangzhou 310012,China)
出处 《高电压技术》 EI CAS CSCD 北大核心 2018年第11期3736-3742,共7页 High Voltage Engineering
关键词 XLPE电缆 双回路 接地方式 交叉互联 感应电压 护层环流 混合排列 XLPE cables two-circuit arranged grounding modes cross-bonding induced voltage circulating current insheaths mixed arrangement
  • 相关文献

参考文献11

二级参考文献102

共引文献246

同被引文献228

引证文献21

二级引证文献127

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部