补风量对地下狭长空间机械排烟效果的影响 被引量:1

Effect of supplementary air volume on mechanical smoke exhaustion in underground long and narrow corridors
原文传递
导出
摘要 地下狭长空间发生火灾,高温烟气不能及时排除,人员不易疏散,危害极大,合理设计补风系统能有效提高机械排烟效率,抑制火灾危害。以某地下工程为例,通过数值模拟研究了机械补风量对狭长走廊机械排烟效果的影响,结果表明,地下狭长空间的补风量不宜过大,对于所选模型最佳补风量应为排烟量的50%到60%之间。针对该结果,进而提出了地下狭长空间补风系统的优化设计方案。 When fire occurs in underground long and narrow sapce,high temperature flue gas can not be exhausted,and personnel evacuation is not easy,which will cause great harm.The reasonable design of the ventilation system in underground long space can effectively improve the efficiency of mechanical smoke exhaustion.Taking an underground project as an example,the influence of mechanical ventilation volume on mechanical smoke exhaust in narrow corridor is studied by numerical simulation.The results show that the air supplement volume of the underground long space should not be too large,the best air supplement volume should be between 50%and 60%of the smoke exhaust volume for the selected model.According to the results,the optimal scheme of underground ventilation system in long and narrow space is put forward.
作者 向健宇 茅靳丰 毛维 余南田 邓忠凯 XIANG Jianyu;MAO Jinfeng;MAO Wei;YU Nantian;DENG Zhongkai(College of Defense Engineering,The Army Engineering University of PLA,Nanjing 210007,China;Research Institute for National Defense Engineering of Academy of Military Sciences PLA China,Beijing 100850,China;Unit 75714 PLA,Hengyang 421900,China))
出处 《防护工程》 2018年第2期35-40,共6页 Protective Engineering
关键词 补风 机械排烟 狭长空间 数值模拟 air supply mechanical smoke exhaustion long and narrow space numerical simulation
  • 相关文献

参考文献6

二级参考文献44

  • 1李元洲,易亮,霍然,周允基.大空间内机械排烟效果的实验研究[J].自然灾害学报,2004,13(4):151-155. 被引量:14
  • 2邹高万,谈和平,刘顺隆,周允基.船舶大空间舱室火灾烟气填充研究[J].哈尔滨工程大学学报,2007,28(6):616-620. 被引量:25
  • 3张梅红,陈立民.地下商场防排烟设计补风方案研究[J].消防科学与技术,2007,26(4):402-403. 被引量:4
  • 4MCGRATTAN K B, FORNEY G P. Fire dynamics simulator (version 4) user' s guide [ R ]. NIST Special Publication 1019. Gaithersburg, USA, 2006.
  • 5MCGRATTAN K B. Fire dynamics simulator (version 4 ) technical reference guide [ R ]. NIST Special Publication 1018. Gaithersburg, USA, 2006.
  • 6PEACOCK R D, DAVIS S, BABRAUSKAS V. Data for room fire model comparisons [ J ]. Journal of Research of the National Institute of Standards and Technology, 1991, 96 (4) :411-462.
  • 7FORNEY G P, MCGRATTAN K B. User' s guide for smoke- view version 4 - a tool for visualizing fire dynamics simulation data [ R ]. NIST Special Publication 1017. Gaithersburg, USA, 2006.
  • 8Leung S K,Kazama D B,Pierson R E,et al. Thermal-induced venti- lation applications in atria:a state of art report[R]. Eureka Labora- tories, Inc,U. S. A, 1981.
  • 9NFPA 92B, Guide for smoke management Systems in malls, atria and large areas[S].
  • 10Craig Studer, Joshua D Greene. Atrium smoke control design and eonstruction principles[J]. Engineered Systems, 2003,6 : 74- 82.

共引文献39

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部