摘要
Magnetic-valve controllable reactor(MCR)has characteristics of DC bias and different types of magnetic flux density in the magnetic circuit and winding current distortion.These characteristics not only lead to loss calculation method of MCR different from that of power transformer,but also make it more difficult to calculate the core loss and wingding loss of MCR accurately.Our study combines core partition method with dynamic inverse J-A model to calculate the core loss of MCR.The winding loss coefficient of MCR is proposed,which takes into account the influence of harmonics and magnetic flux leakage on the winding loss of MCR.The result shows that the proposed core loss calculation method and winding loss coefficient are effective and correct for the loss calculation of MCR.
基金
National Natural Science Foundation of China(No.51367010)
Science and Technology Program of Gansu Province(No.17JR5RA083)
Program for Excellent Team of Scientific Research in Lanzhou Jiaotong University(No.201701)。