摘要
为准确分析某敞开式变电站750 kV接地开关在大风天气下异常合闸原因,本文通过现场检查、接地开关动作过程分析、结构件材质分析、受力情况分析,确定了该接地开关异常合闸故障原因为曲臂螺栓尺寸设计不合理及材质不符合要求导致螺栓松脱.最后基于故障分析结果开展针对性验证试验,制定防范措施,确保了设备安全运行.
In order to accurately analyze the earthing switch failure causes in windy weather,through the onsite inspection,action process analysis,material analysis of structural parts and the stress condition analysis,this paper confirms that the failure reason of the abnormal closing of this earthing switch is the loosened bolt caused by the unreasonable size design of the crank arm bolt and the unqualified material.Furthermore,the targeted validation tests and preventive measures are carried out to ensure the safe operation of the equipment.
作者
李娜
马飞越
牛勃
相中华
倪辉
刘博
LI Na;MA Fei-Yue;NIU Bo;XIANG Zhong-Hua;NI Hui;LIU Bo(Yinchuan College, China University of Mining and Technology, Yinchuan 750001, China;Institute of Electric Power Sciences, Ningxia Electric Power Co. Ltd., Yinchuan 750002, China;State Grid Ningxia Electric Power Co. Ltd., Yinchuan 750002, China)
出处
《四川大学学报(自然科学版)》
CAS
CSCD
北大核心
2020年第6期1131-1136,共6页
Journal of Sichuan University(Natural Science Edition)
基金
宁夏银川机电能源装备专业群资助项目(SGNXDK00PJJS1700013)。