期刊文献+

反硝化深床滤池工艺在污水深度处理中的脱氮研究 被引量:6

Denitrification of Advanced Wastewater Treatment in Deep-bed Filter
下载PDF
导出
摘要 通过对某城市污水厂反硝化深床滤池的运行研究,分析了m(C)/m(N)值、滤池HRT及DO等对脱氮效果的影响。结果表明m(C)/m(N)值大于5时,会影响脱氮效果,导致COD去除率降低,HRT为30min时,最适合该处理工艺的脱氮,并且建议采取措施减少跌水复氧,确保脱氮效果,减少复氧消耗的外加碳源。 The analysis process about effects of C/N,HRT and DO in filter on nitrogen removal were carried out in a municipal WWTP.The study shows that the removal efficiency of nitrogen and COD will be lower,when C/N>5 and the HRT=30 min is most suitable.It is suggested that reducing reoxygenation to ensure the effect of nitrogen removal,meanwhile reduce the consumption of additional carbon sources.
作者 蒋悦 花春文 Jiang Yue;Hua Chunwen(School of Materials and Environmental Protection,Chengdu Textile College,Sichuan Chengdu 611731;Sichuan Zhongce Environmental Technology Co.,Ltd.,Sichuan Chengdu 610036)
出处 《云南化工》 CAS 2020年第12期58-60,共3页 Yunnan Chemical Technology
关键词 反硝化深床滤池 外加碳源 HRT DO 脱氮 deep-bed filter dosage of external carbon source HRT DO denitrification