期刊文献+

基于离散小波分析与K-means聚类算法的MMC-HVDC输电线路保护方案 被引量:14

MMC-HVDC transmission line protection scheme based on discrete wavelet analysis and K-means clustering algorithm
下载PDF
导出
摘要 随着以风电、光伏为代表的可再生能源的持续发展,柔性直流输电系统由于能够清洁高效地对其进行远距离大容量输送而得到了大力的发展。快速、准确地识别故障区域并判别故障类型,实现兼具选择性、速动性、灵敏性和可靠性的直流线路保护方案是柔性直流输电系统发展的迫切需要。理论分析表明,MMC-HVDC输电系统直流线路故障时,线路平波电抗器两侧的暂态电压存在明显差异。采用离散小波分析提取线路平波电抗器两侧的暂态电压有效值进行比较,从而对区内、区外故障进行判别。随后采用K-means聚类算法,利用不同故障类型、不同故障位置,在直流线路故障发生后较短的时间窗口采集得到单侧保护单元电压、电流数据,对其进行聚类分析,获取这些数据的质心与阈值,经过训练,确定相应的保护判据,实现故障选极。PSCAD的仿真结果表明,该保护方案不受故障位置、过渡电阻的影响,能够快速准确地检测MMC-HVDC输电线路故障,识别出故障类型。 With the continuous development of renewable energy represented by wind power and photovoltaic,flexible DC transmission systems have been vigorously developed in recent years due to the ability of clean and efficiently transport of long-distance and large-capacity renewable energy.Fast and accurate identification of fault areas and determination of fault types,achieving DC line protection schemes with selectivity,quickness,sensitivity and reliability are urgent needs for the development of flexible DC transmission systems.Theoretical analysis shows that there are significant differences in transient voltage across the line smoothing reactor when the DC line of the modular multilevel converter high voltage direct current(MMC-HVDC)transmission system fault happens.Discrete wavelet analysis is adopted to extract the RMS values of the transient voltages on both sides of the line smoothing reactor for comparison,so as to distinguish the faults in and outside the protection area.Then,the K-means clustering algorithm is adopted,the voltage and current data of single-ended protection unit collected in a short time window after DC line faults occur are collected from different fault types,different fault locations.And clustering analysis is carried out to obtain the centroid and threshold of these data.After the process of data training,the corresponding protection criteria are determined to realize the identification of the fault poles.And the simulation results of PSCAD/EMTDC show that the protection scheme is not affected by the fault location and transition resistance,which can quickly and accurately detect the faults of the MMC-HVDC transmission lines and identify fault type.
作者 尚学军 霍现旭 郑晓冬 贺杨烊 Shang Xuejun;Huo Xianxu;Zheng Xiaodong;He Yangyang(Electric Power Research Institute of State Grid Tianjin Electric Power Company,Tianjin 300130,China;School of Electronic Information and Electrical Engineering,Shanghai Jiao Tong University,Shanghai 200240,China)
出处 《电测与仪表》 北大核心 2020年第24期52-57,共6页 Electrical Measurement & Instrumentation
基金 国家电网有限公司总部科技项目(KJ20-3-1)。
关键词 离散小波分析 聚类算法 质心 阈值 MMC-HVDC 输电线路 discrete wavelet analysis clustering algorithm centroid threshold MMC-HVDC transmission line
  • 相关文献

参考文献9

二级参考文献103

  • 1高强,林烨,黄立超,罗伟.舟山多端柔性直流输电工程综述[J].电网与清洁能源,2015,31(2):33-38. 被引量:75
  • 2徐政.屠卿瑞,管敏渊,等.柔性直流输电系统[M].北京:机械工业出版社.2013.
  • 3DE AMORIM R C,MIRKIN B.Minkowski metric,feature weighting and anomalous cluster initializing in k -means clustering[J].Pattern Recognition,2012,45(3):1061-1075.
  • 4赵婉君.高压直流输电丁程技术[M].北京:中国电力出版社.2010.
  • 5ZHU Jiebei, CAMPBELL B. Future multi-terminal HVDC trans- mission system using voltage source converters [ C]//The 45th International Universities Power Engineering Conference (UP- EC), Cardiff, Wales, Aug. 31-Sept. 3, 2010. IEEE, 2010:1 -6.
  • 6GEMME L B, DORN J, RETZMANN D, et al. Prospects of multilevel VSC technologies for power transmission [ C ]// IEEE/PES Transmission and Distribution Conference and Expo- sition, Chicago, April 21 - 24, 2008. IEEE, 2008 : 1 - 16.
  • 7ZHANG Lidong, HARNEFORS L, NEE H P. Interconnection of two very weak AC systems by VSC-HVDC links using power- synchronization control [ J ]. IEEE Transactions on Power Sys- tems, 2011, 26(1): 344 -355.
  • 8HORLE N, ERIKSSON K. Electrical supply for offshore instal- lation made possible by use of VSC technology [ C ]//CIGRE Conference, Paris, France, 2002:276 -281.
  • 9ARJEN A, HENDRIKS R L, KLING W L. Combined stability and electro-magnetic transients simulation of offshore wind power connected through multi-terminal VSC-HVDC [ C ]//IEEE Pow- er and Society General Meeting, Minneapolis, July 25 -29, 2010. IEEE, 2010: 1-7.
  • 10LESNICAR A, MARQUARDT R. An innovative modular multi- level converter topology suitable for a wide power range [ C ]// Power Tech Conference Proceedings, Bologna, June 23 - 26, 2003. IEEE, 2003 : 1 - 6.

共引文献353

同被引文献230

引证文献14

二级引证文献107

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部