摘要 对某35kV开关站送出线路故障进行了分析,发现多回送出回路敷设方式不正确极易造成相间电流不平衡,进而引起电站跳闸事故.多回送出线路在采取“品”字形布置及合理的敷设方式后,能有效避免相间电流不平衡,避免零序电流动作,可有效防止电站跳闸事故发生. Based on an analysis of transmission line fault in a 35 kV switching station,it is found that the improper laying mode of multi-circuit transmission circuit can easily cause imbalance of interphase current,and then cause tripping accidents of power stations.After adopting the layout of "品" shape and reasonable laying mode,multi-circuit transmission line can effectively avoid imbalance of interphase current,avoid zero sequence current action,and effectively prevent the occurrence of tripping accidents in power stations.
作者 岳克明 刘珊 杨华 YUE Keming;LIU Shan;YANG Hua(Shanxi Electric Power Engineering Co.,Ltd.of China Energy Engineering Group,Taiyuan,Shanxi 030001,China;Electric Power Research Institute of State Grid Shanxi Electric Power Company,Taiyuan,Shanxi 030001,China)
出处 《山西电力》 2020年第6期59-61,共3页 Shanxi Electric Power
关键词 多回送出线路 相间电流不平衡 跳闸事故 电缆敷设 multi-circuit transmission line imbalance of interphase current tripping accidents cable laying