期刊文献+

基于地理信息的配电网感应雷闪络风险评估

Risk Assessment on Induced Lightning Flashover of Distribution Network Based on Geography Information
下载PDF
导出
摘要 感应雷过电压是10 kV配电网跳闸和停运的主要原因。为评估其风险,首先,建立了感应雷过电压的电磁暂态仿真模型,分析了雷击距离、雷电流幅值、土壤电阻率对过电压幅值的影响,据此提出了一种感应雷过电压幅值简化计算方法;然后,根据输配电线路杆塔坐标、土壤电阻率和雷电流幅值概率密度,建立配电网杆塔闪络概率计算模型;最后,结合地闪密度构建感应雷闪络风险评估模型。 Induced lightning overvoltage is the main reason for the tripping and shutdownn of 10 kV distribution network.Inorder to assess the risk,the electromagnetic transient simulation model of induced lightning overvoltage is established firstly.The influences of lightning distance,lightning current amplitude and soil resistivity on the overvoltage amplitude are analyzed,and a simplified calculation method for induced lightning overvoltage amplitude is proposed.And then,according to the tower coordinates,soil resistivity and probability density of lightning current amplitude of transmission and distribution lines,the calculation model for lightning flashover probability of distribution network tower is established.Finally,the risk assessment model of induced lightning flashover is constructed combined with the lightning density.
作者 雷潇 陈梦军 刘小江 廖文龙 刘强 Lei Xiao;Chen Mengjun;Liu Xiaojiang;Liao Wenlong;Liu Qiang(State Grid Sichuan Electric Power Research Institute, Chengdu 610041, Sichuan, China;State Grid Zigong Electric Power Supply Company, Zigong 613000, Sichuan, China)
出处 《四川电力技术》 2021年第1期1-4,76,共5页 Sichuan Electric Power Technology
基金 国网总部项目5500-202037100A-0-0-00(川藏高海拔地区电网雷电基础参数综合分析与工程化应用研究)。
关键词 地理信息 配电网 感应雷过电压 风险评估 geography information distribution network induced lightning overvoltage risk assessment
  • 相关文献

参考文献4

二级参考文献46

  • 1黄华.20kV电网氧化锌避雷器的正确选用[J].电力安全技术,2004,6(7):17-18. 被引量:1
  • 2徐政.耦合长线电磁暂态分析的扩展Bergeron模型[J].中国电机工程学报,1996,16(5):354-357. 被引量:21
  • 3区伟潮.10kV配电用避雷器故障分析[J].高电压技术,2006,32(7):127-128. 被引量:30
  • 4Sundaram A. Power quality implications of distributionconstruction[R]. California: EPRI,2004.
  • 5YokoyamaS.配电线路雷害对策[M].吴国良,译.北京:中国电力出版社,2008: 14-24.
  • 6Chowdhuri P. Estimation of flashover rates of overheadpower distribution lines by lightning strokes to nearbyground[J]. IEEE Transactions on Power Delivery,1989,4(3): 1982-1989.
  • 7Eriksson A J, Stringfellow M F,Meal D V. Lightning-induced overvoltages on overhead distribution lines[J]. IEEE Transactions on Power Apparatus and Systems,1982,PAS-101: 960-969.
  • 8DL/T 620-1997.交流电气装置过的电压保护和绝缘配合[S].北京:中国电力出版社,1997.
  • 9Society T A D C. IEEE Std 1410-2010 IEEE guide forimproving the lightning performance of electric poweroverhead distribution lines[S]. New York: The Institute ofElectrical and Electronics Engineers, Inc, 2010.
  • 10Chowdhuri P,Gross E T B. Voltage surges induced onoverhead lines by lightning strokes [J]. Proceedings of theInstitution of Electrical Engineers, 1967,114(12):1899-1907.