摘要
针对电网信息物理系统可能遭受的恶性数据注入攻击以及海量的测控数据和复杂的运行方式,提出了一种线下优化部署相量测量单元(PMU)的保护方案。以线性恶性数据注入攻击模型为例,首先采用行最简形矩阵转换方法建立了一套攻击者为攻击指定数量状态量的最小代价攻击模型。然后,针对最小代价攻击模型,提出了一种有效防御并保证全系统可观的相量测量单元优化部署策略;为使该保护策略能够运用于大型电网,提出了一种分区自治保护方案。最后通过IEEE 9节点、IEEE 14节点和IEEE 30节点系统算例验证了所提线下保护模型的有效性。
Aiming at the malicious data injection attack&massive measurement and control data and complex operation mode that cyber physical system may suffer,a protection scheme of offline optimized deployment phasor measurement unit(PMU)is proposed.Taking the linear malicious data injection attack model as an example,a set of minimum cost attack model for the attacker to specify the number of states for the attack is firstly established by using the transformation method of row minimax matrix.Then,based on the least cost attack model,an optimal deployment strategy of phasor measurement unit is proposed which can effectively defend and ensure the overall system's observability,which guarantees the system considerable.In order to make the protection strategy applicable to large power grids,a regional autonomous protection scheme is proposed.Finally,examples of IEEE-9 node,IEEE-14 node and IEEE-30 node systems are presented to verify the effectiveness of the proposed off-line protection model.
作者
常鹏
吴泽群
孙文仲
赵明江
张子炎
CHANG Peng;WU Zequn;SUN Wenzhong;ZHAO Mingjang;ZHANG Ziyan(Northeastern University,Shenyang 110004,China;State Grid Liaoning Electric Power Company,Shenyang 110004,China;State Grid Liaoning Electric Power Materials Co.Ltd.,Shenyang 110004,China)
出处
《智慧电力》
北大核心
2021年第6期60-66,74,共8页
Smart Power
基金
国家重点研发计划资助项目(2018YFA070145)。
关键词
信息物理系统
恶性数据注入攻击
相量测量单元
线下保护
分区自治
cyber physical system
malicious data injection attacks
phasor measurement unit
offline protection
partition of autonomy