期刊文献+

电力系统合并单元测试仪测量误差检测校准装置研制及性能分析 被引量:13

Development and performance analysis of a measurement error test and calibration device for a merging unit tester in a power system
下载PDF
导出
摘要 为推进智能变电站建设,针对合并单元测试仪测量误差缺少验证手段导致的电力系统合并单元等关键二次设备应用和推广受影响的问题,研制了一种针对合并单元测试仪测量误差开展检测校准的装置。首先,分析现有方法弊端,提出合并单元测试仪测量误差检测校准的整体思路,明确设计方案。其次,基于高精度硬件采集回路和高分辨率ADC同步采样技术,实现模拟信号高精度采样和数字信号高精度输出,解决了信号源的问题。最后,基于精确时间戳技术和采样值校正算法,实现A/D误差的高精度、宽量程模拟,该误差可作为合并单元测试仪测量的基准误差。试验及工程验证结果表明,新研制装置的采集输出、A/D误差模拟和抗干扰能力满足标准要求和应用需求,有效解决了合并单元测试仪测量误差无法检测校准的行业难题,填补空白,提高了检测校准能力和效率。 There is a problem that the application and popularization of key secondary equipment such as a power system merging unit are affected by the lack of verification means for the measurement error of a merging unit tester.Thus a device for testing and calibrating such measurement error is developed.This is an important step in the promotion of intelligent substation construction.First,the disadvantages of the existing methods are analyzed.Then the overall idea of the measurement error test and calibration for the merging unit tester is proposed,and the design scheme is clarified.Secondly,based on a high-precision hardware acquisition loop and high-resolution ADC synchronous sampling technology,high-precision sampling of analog signal and high-precision output of the digital signal are realized to solve the problem of signal source.Finally,based on accurate timestamp technology and a sampling value correction algorithm,the high-precision and wide-range simulation of A/D error are realized as the reference error measured by the merging unit tester.Test and engineering verification results show that the acquisition output,A/D error simulation and anti-interference ability of the newly developed device meet the standard and application requirements,effectively solve the industry problem outlined above,and fill a gap,and improve test and calibration ability and efficiency.
作者 姚致清 王朋飞 陈光华 张杨 穆小亮 庞涛 贺春 YAO Zhiqing;WANG Pengfei;CHEN Guanghua;ZHANG Yang;MU Xiaoliang;PANG Tao;HE Chun(School of Electrical and Mechanical Engineering,Xuchang University,Xuchang 461000,China;Henan Key Laboratory of Relay Protection and Automation,Xuchang 461000,China;Xuchang Ketop Testing Research Institute Co.,Ltd.,Xuchang 461000,China;Zhuhai Ketop Testing Technology Co.,Ltd.,Zhuhai 519000,China;Xuchang KETOP Electrical Research Institute Co.,Ltd.,Xuchang 461000,China)
出处 《电力系统保护与控制》 CSCD 北大核心 2022年第2期119-126,共8页 Power System Protection and Control
基金 国家自然科学基金项目资助(U1804252)。
关键词 电力系统 合并单元测试仪 幅值误差 相位误差 误差设定 power system merging unit tester amplitude error phase error error setting
  • 相关文献

参考文献19

二级参考文献165

共引文献312

同被引文献184

引证文献13

二级引证文献13

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部