地铁车站出入口环境测试及防结露方案研究

Study on Environmental Test and Anti Condensation Scheme at Entrance and Exit of Subway Station
下载PDF
导出
摘要 本文对南方某地下地铁车站出入口环境进行了测试研究。通过对出入口壁面温度,地面温度,空气温度以及室外空气参数的测试,分析了车站出入口产生结露现象的原因,并给出了相关工程措施建议。测试结果表明:出入口壁面、地面温度低于室外空气露点温度,是造成壁面与地面结露的主要原因。部分长出入口内设置风机盘管,其出风口温度较低,是造成吊顶凝水结露的主要原因。 The entrance and exit environment of an underground subway station in the south was tested and studied. By testing the wall temperature, ground temperature, air temperature and outdoor air parameters, the causes of condensation are analyzed. Relevant engineering measures and suggestions are given. The test results show that:(1) the temperature of the wall and ground at the inlet and outlet is lower than the dew point temperature of the outdoor air, which is the main reason for the condensation of wall and ground;(2) Fan coil units are set in some long inlets and outlets, and the low temperature is the main reason for dew condensation on the ceiling.
作者 孙超 SUN Chao(National Engineering Laboratory for Digital Construction and Evaluation of Urban Rail Transit;China Railway Design Corporation)
出处 《建筑热能通风空调》 2022年第5期71-73,94,共4页 Building Energy & Environment
基金 中国铁路设计集团有限公司科技开发课题(2021A230303)。
关键词 地铁 车站 出入口 环境测试 结露 subway station entrance and exit environmental testing condensation