摘要 针对重庆某高架站台公共区域设计蒸发冷却通风降温系统,在机组出厂前对系统的送风量、降温效果以及风管温升情况进行测试。结果表明,当风机频率在40 Hz时,直接蒸发冷却效率平均值为93.7%,可达到4.8℃的温降,从机组出风口到各送风口存在0.1~1.2℃的温升。最后对系统中存在的一些问题提出改进措施,使该系统具有更好的应用效果。 The evaporative cooling ventilation system for the public area of one elevated platform in Chongqing is designed, and the air volume, cooling effect and temperature rise of the air duct are tested before the unit leaves the factory. The results show that when the fan frequency is 40 Hz, the average direct evaporative cooling efficiency is 93.7%, which can reach a temperature drop of 4.8 ℃, and there is a 0.1-1.2 ℃ temperature rise from the air outlet of the unit to each air supply outlet. Finally, some improvement measures are proposed according to the existing problems in the system, so that the system has a better application effect.
作者 杜妍 黄翔 王红利 靳如意 史东旭 马健 余良 彭彦 Du Yan;Huang Xiang;Wang Hongli;Jin Ruyi;Shi Dongxu;Ma Jian;Yu Liang;Peng Yan(Xi’an Polytechnic University;Chongqing Fuchenxing Technology Corporation)
出处 《制冷与空调》 2022年第8期40-43,55,共5页 Refrigeration and Air-Conditioning
关键词 蒸发冷却 轨道交通 站台公共区域 温降 效率 evaporative cooling rail transit public area of platform temperature drop efficiency
  • 相关文献

参考文献5

二级参考文献42

  • 1我国《地下铁道设计规范》即将颁布施行[J].都市快轨交通,1992,16(2):7-7. 被引量:2
  • 2ARENS E, XU T, MIURA K, et al. A study of occupant cooling by personally controlled air movement [J]. Energy Building, 1998, 27:45- 59.
  • 3CANDIDO C, DEAR R J DE, LAMBERTS R, et al. Air movement acceptability limits and thermal comfort in Brazil's hot humid climate zone [J]. Building and Environment, 2010,45 : 222-229.
  • 4TOMONORI SAKOI, KAZUYO TSUZUKI, SHINSUKE KATO, et al. Thermal comfort, skin temperature distribution, and sensible heat loss distribution in the sitting posture in various asymmetric radiant fields [J]. Building and Environment, 2007, 42 :3984 -3999.
  • 5YAO YE, LIAN ZHIWEI, LIU WEIWEI, et al. Experimental study on physiological responses and thermal comfort under various ambient temperatures[J]. Physiology & Behavior, 2008, 93: 310-321.
  • 6LI BAIZHAN, LI WENJIE,LIU HONG, et al. Physiological expression of human thermal comfort to indoor operative temperature in the NON-HVAC environment[J]. Indoor and Built Environment, 2010, 19(2) : 221-229.
  • 7ASHRAE. ANSI/ASHRAE 55-2004, Thermal environmental conditions for human oceupaney [M]. Atlanta: American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. 2004.
  • 8FERGUS NICOL. Adaptive thermal comfort standards in the hot-humid tropics [J]. Energy and Buildings, 2004, 36: 628-637.
  • 9ISO7730:2005. Ergonomics of the Thermal Environment-- Analytical Determination and Interpretation of Thermal Comfort Using Calculation of the PMV and PPD Indices and Local Thermal Comfort Criteria [S]. Geneva, Switzerland : International Standard Organisation, 2005.
  • 10ISO. International Standard 7726.. Thermal Environment- Instruments and Methods for Measuring Physical Quantities [ S ], Geneva : International Organization for Standardization, 1998.