寒冷地区某数据机房机柜散热测试及仿真模型研究 被引量:1

Research on Heat Dissipation Test and Simulation Model of the Cabinet in a Data Room in Cold Area
下载PDF
导出
摘要 为了解数据机房机柜排风温度的特点,详细掌握数据机房热环境特征,文章对寒冷地区某办公楼用数据机房机柜送排风情况开展测试和CFD模拟研究。测试结果表明,机柜进风口温度为16℃时,机柜进出口空气温差为12℃左右;本例中数据机房冷热通道未封闭,结果显示机柜进风侧和出风侧空气温度均随垂直距离的增加而升高,冷热气流的掺混会导致数据机房冷量过度消耗。通过CFD模拟对气流组织形式进行合理设计,有利于降低数据机房制冷能耗。 In order to understand the characteristics of the exhaust temperature of the cabinet in the data room and master the thermal environment parameters of the data room, this paper carries out a test and CFD simulation study on the air supply and exhaust of the cabinet in the data room of an office building in cold area. The results show that when the inlet temperature of the cabinet is 16 ℃,the air temperature difference of the inlet and outlet of the cabinet is around 12 ℃. In this example, the cold and hot channels are not closed in this data room, the results show that the air temperature of the inlet side and outlet side of the cabinet increases with the increasing of vertical distance. The mixing of cold and hot air flow leads to excessive cold consumption in the data room. The reasonable design of air distribution through CFD simulation is conducive to reducing the cooling energy consumption in a data room.
作者 李国柱 崔美华 李忠辉 王天来 赵乃妮 LI Guo-zhu;CUI Mei-hua;LI Zhong-hui;WANG Tian-lai;ZHAO Nai-ni(China Academy of Building Research;School of Municipal and Environmental Engineering,Shenyang Jianzhu University;Liaoning Provincial Building Design&Research Institute;Beijing Engineering Technology Research Center of Green Building Design)
出处 《智能建筑与智慧城市》 2022年第11期144-146,共3页 Intelligent Building & Smart City
基金 国家自然科学基金项目,项目编号:52008386。
关键词 数据机房 机柜散热 气流组织 数值模拟 data room cabinet heat dissipation air distribution numerical simulation
  • 相关文献

参考文献5

二级参考文献40

  • 1黄翔.国内外蒸发冷却空调技术研究进展(1)[J].暖通空调,2007,37(2):24-30. 被引量:161
  • 2中国电子工程设计院.GB50174-2008电子信息系统机房设计规范[S].北京:中国计划出版社,2009.
  • 3Sharma R K, Bash C E, Patel C D. Dimensionless parameters for evaluation of thermal design and performance of large scale data centers [C]// Proceedings of the American Institute of Aeronautics and Astronautics (AIAA), St. Louis, MO, 2002, Paper AIAA- 2002- 3091.
  • 4Bash C E, Patel C D, Sharma R K. Efficient thermal management of data centers immediate and long term research needs [J]. Int. J. Heating, Ventilating, Air Conditioning and Refrigeration Research, 2003, 9 (2) : 137- 152.
  • 5Magunus K. Herrlin. Airflow and Cooling Performance of Data Centers: Two Performance Metrics [J]. ASHRAE Transactions, 2008, 114 (2) : 182-187.
  • 6TC 9.9 - Mission Critical Facilities, 2005. Thermal Guidelines for Data Processing Environments. ASHRAE.
  • 7云计算发展与政策论坛.数据中心能效测评指南[C].2012.
  • 8Environmental Protection Agency. Report to congress on server and data center energy efficiency [-R. Public Law 109-431. U S, 2007.
  • 9Sun H S, Lee S E. Case study of data centers' energy performance[J. Energy and Buildings, 2006,38 (5) . 522-533.
  • 10Koomy J G. Growth in data center electricity use 2005 to 2010 EEB/OL. E2011 http: /// www. analyticspress, eom/datacenters, html.

共引文献109

同被引文献2

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部