民用建筑耐火电缆选择应注意的问题 被引量:2

Attention in Selection of Fire-resistant Cables in Civil Buildings
下载PDF
导出
摘要 分析设计对消防供电电缆耐火类参数的要求与目前国内外耐火试验标准参数值的差别,以及部分设计人员在电缆选择认识上的偏差,建议行业尽快编制公信力强的国家级耐火试验标准,也建议设计人员应该基于现行规范、标准和产品,做到设计有据。 The design requirements for fire resistance parameters of power supply cable for fire protection,the existing differences between domestic and foreign fire-resistant test standard parameters and the deviations of some designers in the understanding of cable selection are analyzed,the industry is suggested to develop national fire test standards with strong credibility and the designers are also suggested to make design based on current specifications,standards and products.
作者 陈剗 CHEN Chan(Chengdu Architectural Design&Research Institute Co.,Ltd.,Chengdu 610041,China)
出处 《建筑电气》 2022年第12期18-22,共5页 Building Electricity
关键词 消防配电线路 矿物绝缘电缆 耐火电缆 耐火试验标准 有机绝缘类电缆 柔性矿物绝缘电缆 耐火温度 耐火时间 power distribution line for fire protection mineral-insulated cable fire-resistant cable fire test standard organic insulated cables flexible mineral-insulated cable fire resistance temperature fire resistance time
  • 相关文献

参考文献9

二级参考文献20

  • 1唐崇健.矿物绝缘电缆的特性及相关电气规范的采用[J].电线电缆,2004(6):10-13. 被引量:4
  • 2赵华利,王伯涛,戴殿峰.防火电线电缆的分类特性及试验方法[J].消防科学与技术,2005,24(2):220-223. 被引量:28
  • 3公安部四川消防研究所.GA306.2-2007阻燃及耐火电缆塑料绝缘阻燃及耐火电缆分级和要求第2部分:耐火电缆[S].北京:中国标准出版社.2007.
  • 4IEC 331- 1970 Fire-resistant Characteristics of Cable [S], 1970.
  • 5IEC 60331. 11 - 1999 Tests for electric cables under fire conditions - Circuit integrity - Part 11: Apparatus- Fire alone at a flame temperature of at least 750 ℃ [S], 1999.
  • 6BS 6387: 2013 Test method for resistance to fire of cables required to maintain circuit integrity under fire conditions [S], 2013.
  • 7BS 8491: 2008 Method for assessment of fire integrity of large diameter power cables for use as components for smoke and heat control systems and certain other active fire safety systems [S], 2008.
  • 8IEC 60331-1: 2009 Tests for electric cables under fire conditions- Circuit integrity- Part 1: Test method for fire with shock at a temperature of at least 830 -12 for cables of rated voltage up to and including O, 6 / 1, 0 kV and with an overall diameter exceeding 20 ram[S], 2009.
  • 9IEC 60331- 2:2009 Tests for electric cables under fire conditions- Circuit integrity- Part 2: Test method for fire with shock at a temperature of at least 830℃ for cables of rated voltage up to and including O, 6 /1,0 kV and with an overall diameter not exceeding 20 mm [S], 2009.
  • 10上海电缆研究所.GB/T19216.31-2008在火焰条件下电缆或光缆完整性试验第31部分:供火并施加冲击的试验程序和要求额定电压0.6,1kV及以下电缆[S].北京:中国标准出版社,2009.

共引文献21

同被引文献13

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部