期刊文献+

±800 kV特高压直流线路地线断线故障分析

Analysis of Ground Wire Disconnection Fault of±800 kV Ultra-High Voltage DC Line
下载PDF
导出
摘要 提升抗冰能力对线路安全运行至关重要。对某±800 kV特高压直流线路地线断线故障现场的环境及录波进行了分析,开展了地线断口静态分析及扫描电镜试验、拉断力试验,并对导地线间距进行了仿真计算。试验和仿真计算表明:特高压直流导地线覆冰厚度差异较大,随着地线覆冰厚度的增加,导地线间间距逐渐减小,在大风作用下极易发生空气间隙不足放电。本次特高压线路故障原因为重覆冰引起导地线空气间隙距离不足,导致放电烧伤和拉断地线。微地形区线路覆冰情况可能超过设计值,应考虑现场实际覆冰厚度、导地线覆冰厚度差值、故障区段微气象和微地形等因素,确保线路设计运行有充足裕度。 To improve the anti-icing ability is vital for safe operation of the line.The paper analyzes the environment and waveform record of the ground wire disconnection fault field of±800 kV ultra-high voltage(UHV)DC line,makes static analysis of the ground wire fracture,conducts scanning electron microscope and breaking force test,and carries out the simulation calculation of guide wire spacing.According to the test and simulation calculation,there is a big difference of the ground wire icing thickness of UHV DC.When the ground wire icing thickness increases,the spacing between conductors and ground wires gradually decreases which is likely to contribute to discharge because of insufficient air gap under the strong wind.The reason for this UHV line fault is that the insufficient air gap of ground wires caused by icing contributes to discharge to burn and break ground wires.The line icing of micro-terrain region is possible to exceed the design value,so factors such as the actual on-site icing thickness,ground wire icing thickness differential value,micro-meteorology and micro-topography of fault section should be taken into consideration to ensure operation of the line.
作者 魏小龙 张璐 闫可为 李新民 韩彦华 李伟 孔志战 WEI Xiao-long;ZHANG Lu;YAN Ke-wei;LI Xin-min;HAN Yan-hua;LI Wei;KONG Zhi-zhan(State Grid Shaanxi Electric Power Co.,Ltd,Xi’an 710048,China;Electric Power Research Institute of State Grid Shaanxi Electric Power Co.,Ltd,Xi’an 710100,China;Ultra High Voltage Company of State Grid Shaanxi Electric Power Co.,Ltd,Xi’an 710075,China)
出处 《电工电气》 2023年第2期41-46,共6页 Electrotechnics Electric
基金 国家电网公司科技项目(5226SX22000V) 国网陕西省电力有限公司科技项目(5226KY23000W)。
关键词 ±800 kV特高压直流线路 地线 覆冰 断线 故障分析 ±800 kV ultra-high voltage DC line ground wire icing disconnection fault analysis
  • 相关文献

参考文献18

二级参考文献334

共引文献421

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部