期刊文献+

基于温升特性的强迫导向油循环风冷结构变压器负荷能力评估

Load Capacity Evaluation of Forced Guided Oil Circulation Air-cooled Transformer Based on Temperature Rise Characteristics
原文传递
导出
摘要 针对强迫导向油循环风冷(oir directrd air forced,ODAF)结构变压器负荷能力受温升约束影响的问题,提出了3种负荷类型情况下变压器负荷能力评估方法。首先,考虑风扇与油泵的运行状态以及油粘度变化对热阻的影响等因素,基于热电类比法建立了变压器热路模型,以计算绕组热点与顶部油温度;其次,采用粒子群优化(particle swarm optimization,PSO)算法拟合热路模型参数,并基于2台不同型号变压器的运行数据,对热路模型的计算精度与拟合参数适用性进行有效性验证;最后,参考GB/T1094.7负载导则给出的温升限值,基于温升特性提出了负荷能力评估模型。分析结果表明,该研究所提热路模型计算热点温度的误差不大于2.35℃,在工程允许范围内;正常周期性负荷下当环境温度低于1℃时,关闭1组子散热器后仍满足温升约束。 Aiming at the problem that the load capacity of forced guided oil circulation air-cooled(ODAF)transformer is affected by the temperature rise constraint,this paper proposes three kinds of load capacity evaluation methods for trans-former.Firstly,the running state of fan and oil pump and the influence of oil viscosity change on thermal resistance and other factors are taken into account,and a transformer thermal model is established based on thermoelectric analogy method to calculate winding hot spot and top oil temperature.Secondly,particle swarm optimization algorithm(PSO)is used to fit the parameters of the thermal model;meanwhile,based on the operation data of two different types of trans-formers,the calculation accuracy of the thermal model and the suitability of the fitting parameters are validated.Finally,a load capacity evaluation model based on the temperature rise characteristics is proposed by referring to the temperature rise limit given in the load guide GB/T 1094.7.The analysis results show that the error of hot spot temperature calculated by the proposed model is no more than 2.35℃,which is within the allowable range of engineering.Under normal peri-odic load,when the ambient temperature is lower than 1℃,the temperature rise constraint is still satisfied after closing a group of sub-radiators.
作者 刘刚 兰和潼 姜雄伟 刘云鹏 王文浩 LIU Gang;LAN Hetong;JIANG Xiongwei;LIU Yunpeng;WANG Wenhao(Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense,North China Electric Power University,Baoding 071003,China;Electric Power Research Institute of State Grid Zhejiang Electric Power Company,Hangzhou 310014,China)
出处 《高电压技术》 EI CAS CSCD 北大核心 2024年第1期232-241,I0019,共11页 High Voltage Engineering
基金 国网浙江省电力有限公司科技项目(5211DS220005)。
关键词 负荷能力 ODAF冷却方式 变压器 温升特性 热路模型 load capacity ODAF cooling mode transformer temperature rise characteristic thermal model
  • 相关文献

参考文献7

二级参考文献111

共引文献96

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部