某数据中心机房空调系统测试分析及优化措施

Test Analysis and Improvement Measures of Air Conditioning Systems in a Data Center
下载PDF
导出
摘要 以某数据中心机房为例,通过对数据中心机房内空调系统运行时的温度、湿度、风量进行测试,对其测试方法及测试结果进行分析,总结了该数据中心机房空调系统存在的问题,并根据测试结果提出优化改进措施。提出了恒湿机选型及空调选型时需注意的问题以及推荐的风量测量方法,为今后数据中心的设计、运维提供一定的参考。 Taking a data center computer room as an example,it analyzes the test method and test content by testing the temperature,humidity and air volume of the data center room during operation,summarizes the existing problems of the air conditioning systems,and proposes some improvement measures based on the test results.It proposes the issues when selecting con-stant humidity dehumidifier and humidifier and air conditioner,as well as the recommended air volume measurement method,which provides reference for the design and operation of data centers.
作者 景淼 何健 董青 Jing Miao;He Jian;Dong Qing(China Unicom Digital Technology Co.,Ltd.,Beijing 100085,China)
出处 《邮电设计技术》 2024年第2期88-92,共5页 Designing Techniques of Posts and Telecommunications
关键词 数据中心 空调系统 温湿度 风量 气流组织 Data center Air conditioning system Temperature and humidity Air volume Air distribution