期刊文献+

华龙一号主控室可居留区气密性试验研究

Research on Airtightness Test of Habitable Zone in Main Control Room of HPR1000
原文传递
导出
摘要 基于恒定流量法,对主控室可居留区气密性试验从试验方法选择、示踪气体注入及取样方法、平衡浓度、试验结果计算等多个维度展开了研究,并在卡拉奇核电项目K2/K3机组进行了改进及应用。结果表明,通过研究正压与风量差值的关系,得出了执行试验的理想正压区间为35~50 Pa;通过研究示踪气体混合均匀性影响因素,确定了正压与内漏量的关系,并得出了执行试验的理想正压值约为50 Pa;通过研究正压与风量差值的关系,得出了执行试验的理想正压区间为35~50 Pa;在此基础上,通过示踪气体浓度数据对比分析,分析了浓度的波动幅度及规律,提出了促进示踪剂平衡的有效措施,即增加混流设备可以使示踪气体浓度充分均匀,减小浓度的波动幅度。 Based on the constant flow method,research was conducted on the airtightness test of the habitable area in the main control room from multiple dimensions such as test method selection,tracer gas injection,sampling method,equilibrium concentration,and calculation of test results.Improvements and applications were made to the K2/K3 unit of the Karachi nuclear power project.The results showed that by studying the factors affecting the uniformity of tracer gas mixing,the relationship between positive pressure and internal leakage was determined,and the ideal positive pressure value for conducting the experiment was approximately 50 Pa;By studying the relationship between positive pressure and air volume difference,it was found that the ideal positive pressure range for conducting the experiment is 35~50 Pa;By analyzing the relationship between positive pressure and internal leakage,the ideal positive pressure value for conducting the experiment was obtained;On this basis,through comparative analysis of tracer gas concentration data,the fluctuation amplitude and pattern of concentration were analyzed,and effective measures to promote tracer balance were proposed.That is,adding mixed flow equipment can make the tracer gas concentration fully uniform and reduce the fluctuation amplitude of concentration.
作者 许福南 王广军 吴樱 Xu Funan;Wang Guangjun;Wu Ying(School of Energy and Power Engineering,Chongqing University,Chongqing,400044,China;East China Branch of China Nuclear Power Engineering Co.,Ltd.,Jiaxing,Zhejiang,314300,China)
出处 《核动力工程》 EI CAS CSCD 北大核心 2024年第2期231-234,共4页 Nuclear Power Engineering
关键词 主控室 可居留 气密性 恒定流量 平衡浓度 Main control room Habitable Air tightness Constant flow Equilibrium concentration
  • 相关文献

参考文献2

二级参考文献12

  • 1US NRC. Title 10, code of Federal Regulations, Appendix A to part 50 - general design criteria for nuclear power plant[ R].
  • 2US NRC. Evaluating the habitability of a nuclear power plant control room during a postulated hazardous chemical release [ S ]. Regulatory Guide 1.78. Revision 1. 2002.
  • 3US NRC. Protection of nuclear power plant control room operators against an accidental chlorine release [ S]. Regulatory Guide 1.95. Revision 1. 1977.
  • 4US NRC. Demonstrating control room envelope integrity at nuclear power reactors [ S ]. Regulatory Guide 1. 197. 2003.
  • 5US NRC. Control room habitability at light - water nuclear power reactors [ S]. Regulatory Guide 1. 196. 2003.
  • 6Nuclear Energy Institute. Control room habitability assessment guidance [R]. NEI 99-03. Revision 0. 2001.
  • 7American Society for Testing and Materials. Standard test method for determining air change in a single zone by means of a tracer gas dilution [S]. ASTM E741-00. 2006.
  • 8American Society for Testing and Materials.Standard test method for volumetric and mass flow rate measurement using tracer gas dilution [ S ]. ASTM E2029--1999. 2011.
  • 9NUCON. Envelope inleakage testing using the concentration decay test method [ R]. NUCON Procedure 12- 356. Revision 1.
  • 10NUCON. Envelope leakage testing and characterization using the constant injection test method [ R]. NUCON Procedure 12 - 366.