摘要 为探究辐射空调系统供暖特性,搭建辐射空调系统试验台,进行7 d的系统间歇运行试验,对两级新风机组送风温湿度,空气源热泵主机制热量、能效比,以及系统能耗和能效比进行分析。结果表明,在设定参数下,两级新风机组稳定时送风温湿度分别为27℃和35%左右,空气源热泵主机平均制热量为4.5 kW,制热性能系数(COPU)为4.10;辐射空调系统耗电量为1.5 kW·h,系统性能系数(COPS)为3.02。试验结果可为系统的进一步优化和推广提供参考。 To explore the heating characteristics of a radiation air conditioning system,a radiation air conditioning system test bench was built,a 7-day intermittent operation test was conducted.The temperature and humidity of the air from two-stage fresh air unit,the heat output and efficiency of the air-source heat pump,as well as the energy use and efficiency ratio of the system were analyzed emphatically.The results show that under setting parameters,the stable supply air temperature and humidity of the two-stage fresh air are about 27℃and 35%,respectively.The average heating capacity of the air source heat pump host is 4.5 kW,and the heating coefficient of performance(COPU)is 4.10.The power consumption of the radiation air conditioning system is 1.5 kW·h,and the system coefficient of performance(COPS)is 3.02.The results can provide reference for further optimization and promotion of the system.
作者 张恒 傅允准 ZHANG Heng;FU Yunzhun(School of Mechanical and Automotive Engineering,Shanghai University of Engineering Science,Shanghai 201620,China)
出处 《上海工程技术大学学报》 CAS 2024年第2期165-170,共6页 Journal of Shanghai University of Engineering Science
关键词 辐射空调 金属辐射板 两级新风机组 热泵 能效比 radiant air conditioning metal radiant panel two-stage fresh air unit heat pump energy efficiency ratio
  • 相关文献

参考文献10

二级参考文献86

  • 1余志锋.空气膜防结露型空调辐射板的可行性研究[J].建筑节能,2020,48(1):77-79. 被引量:3
  • 2郑树伟,丘林,王文海.调湿建材应用于辐射供冷房间的可行性[J].制冷与空调,2004,4(4):70-73. 被引量:11
  • 3李常河,李永安,刘学来,张晓锋.地板辐射供冷系统地面温度的确定[J].低温建筑技术,2005,27(2):94-95. 被引量:11
  • 4李先中,刘传聚,王子介.置换通风对地板供冷的影响[J].制冷与空调,2004,4(1):48-50. 被引量:5
  • 5孙丽颖 马最良.冷却吊顶空调系统的设计要点[C]..暖通空调新技术(2)[C].北京:中国建筑工业出版社,2000.61-64.
  • 6B. Costelloe, D. finn. Indirect evaporative cooling potential in air - water systems in temperate climates, Energy and Building 35 (2003) 573- 519.
  • 7Atila Novoselac, Jelena Srebric. A critical review on the performance and design of combined cooled ceiling and displacement ventilation systems, Energy and Buildings,34(2002) 497 - 509.
  • 8Claude- Alain Roulet, Jean- Pierre Rossy, Yves Roulet.Using large radiant panels for indoor climate conditioning, Energy and Buildings 30 1999 121 - 126.
  • 9J. L. Nir, L.Z. Zhang. Energy saving potential of chilled -ceiling combined with desiccant cooling in hot and humid climates, Energy and Buildings 34 (2002) 487- 495.
  • 10L. Z. Zhang. Indoors humidity behaviors associated with decoupled cooling in hot and humid climates, Building and Environment 38(2003) 99 - 107.

共引文献97

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部