摘要 为保障消防员职业安全与健康、提升消防员身体素质和训练效果,开展消防员多体征传感器信息融合技术研究。针对生命体征监测设备易受消防实战训练中的恶劣环境、消防员的大幅度作业运动影响和消防员个人防护装备的干扰,造成采集数据的精度降低,导致采集数据无效或缺失的问题,本文采取多模传感器交叉采集消防员体征指标的设计,利用多模传感器从不同位置对消防员的心电波和脉搏波进行监测,并对采集信号进行小波阈值收缩法和快速滑动均值滤波去噪处理,然后基于数据的离散型和连续型分别开展特征识别和融合。经融合后,在功率自行车、大雨环境、消防员滚轮胎和拖拽假人训练等场景中开展测试,表明多模生命体征监测单元的监测精度和容错能力大幅提升。 To ensure the occupational safety and health of firefighters,improve their physical fitness and training effectiveness,research is being conducted on the fusion technology of multi sign sensor information for firefighters.In response to the problem that vital sign monitoring equipment is susceptible to harsh environments during firefighting training,significant work movements of firefighters,and interference from personal protective equipment of firefighters,resulting in reduced accuracy of data collection and ineffective or missing data collection,this article adopts the design of multi-mode sensor cross collection to monitor firefighter physical sign indicators.Multi-mode sensors are used to monitor firefighter′s electrocardiogram and pulse waves from different positions,and the collected signals are denoised using wavelet threshold contraction method and fast sliding mean filtering.Then,feature recognition and fusion are carried out based on the discrete and continuous types of data.After integration,tests were conducted in several scenarios such as power bicycles,heavy rain environments,firefighter tire rolling,and drag dummy training,indicating a significant improvement in the monitoring accuracy and fault tolerance of the multi-mode vital sign monitoring unit.
作者 屈天翊 洪赢政 Qu Tianyi;Hong Yingzheng(National Fire and Rescue Administration,Beijing 100097,China;Shanghai Fire Science and Technology Research Institute of MEM,Shanghai 200032,China)
出处 《消防科学与技术》 CAS 北大核心 2024年第8期1111-1115,共5页 Fire Science and Technology
基金 国家重点研发计划课题(2018YFC0807606)。
关键词 消防员职业安全与健康 多传感器信息融合 消防员生命体征 体征监测 firefighters occupational safety and health multisensor information fusion firefighter vital signs signs monitoring
  • 相关文献

参考文献11

二级参考文献70

  • 1席涛,杨国胜,汤池.呼吸信号检测技术的研究进展[J].医疗卫生装备,2004,25(12):26-28. 被引量:27
  • 2苏志雄,郝选明.心率监测在运动训练中的作用及影响因素[J].成都体育学院学报,2002,28(2):89-91. 被引量:70
  • 3钱竞光,宋雅伟,叶强,李勇强,唐潇.步行动作的生物力学原理及其步态分析[J].南京体育学院学报(自然科学版),2006,5(4):1-7. 被引量:96
  • 4Nijboer J A, Dorlas J C, Mahieu H F. Photoelectric plethysmography-some fundamental aspects of the reflection and transmis sion methods[J]. Clinical Physics and Physiological Measurement, 1981, 2: 205--215.
  • 5Bernardi L. , Radaelli A. , Solda' P L. Autonomic control of skin microvessels: assessment by power spectrum of photoplethysmographic waves[J].Clinic Science, 1996, 90:345-355.
  • 6Anders Johansson, Per Ake Oberg, Gunnar Sedin. Monitoring of heart and respiratory rates in newborn infants using a new photoplethysmographic technique[J].Journal of Clinical Moni toring and Computing, 1999,15 : 461-467.
  • 7Nilsson L, Johansson A, Kalman S. Monitoring of respiratory rate in postoperative care using a new photoplethysmographic technique[J]. Journal of Clinical Monitoring and Computing, 2000,16: 309-315.
  • 8Nilsson L, Johansson A, Kalman S. Respiration can be moni tored by photoplethysmography with high sensitivity and specificity regardless of anaesthesia and ventilatory mode[J].Acta Anaesthesiologiea Scandinavica, 2005,49(8) : 1157 - 1162.
  • 9Nilsson L, Goscinski T, Johansson A. Age and gender do not influence the ability to detect respiration by photoplethysmography[J].Journal of Clinical Monitoring and Computing, 2006, 20(6) :431--436.
  • 10Clifton D, Douglas J G, Addison P S. Measurement of respiratory rate from the photoplethysmogram in chest clinic patients [J]. Journal of Clinical Monitoring and Computing, 2007, 21 (1) : 55--61.

共引文献67

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部