期刊文献+

高压直流输电动态相量建模与仿真 被引量:90

MODELING AND SIMULATION OF HVDC WITH DYNAMIC PHASORS
下载PDF
导出
摘要 文中运用一种新的建模方法——基于时变傅立叶级数的动态相量(Dynamic phasors)法对HVDC进行建模和仿真。该方法通过保留系统状态变量对应的时变傅立叶级数中重要的项而对原系统进行简化,在建模过程中,用开关函数来表示阀的开关状态,换流桥每个桥臂都有3个不同状态,用它们的状态分段组合可以表示整个换流桥的状态,从而可以考虑直流换流桥的换相过程。最后通过简单的算例,将动态相量模型和详细电磁暂态(EMT)模型仿真计算结果相比较,证明HVDC的动态相量模型是精确而有效的,不仅可准确地描述HVDC在给定扰动下暂态变化过程,而且可节省计算时间。 A newly developed method-dynamic phasors method is presented in this paper and applied to model HVDC converters This approach is based on the time-varying Fourier coefficient series of the system variables, and focused on the dynamics of the Fourier coefficients. By truncating unimportant higher order series and keeping only those significant series, the dynamic phasors model can catch the dynamic behavior of the original detail model of a certain element. In this paper, the analysis is based on a piecewise state representation of the converter through the switching functions, which can consider the commutation periods. Through typical test examples and their simulation results, the effectiveness and accuracy of this method are verified.
出处 《中国电机工程学报》 EI CSCD 北大核心 2003年第12期28-32,共5页 Proceedings of the CSEE
基金 国家重点基础研究专项经费项目(G1998020305) 香港政府大学研究基金(CityU 1/00C)~~
关键词 高压直流输电 动态相量 建模 仿真 电力系统 电网 数学模型 Power system HVDC Dynamic phasors Time-varying fourier coefficients
  • 相关文献

参考文献8

  • 1[1]Sanders S R, Noworolski J M, Liu X Z, et al. Generalized averaging method for power conversion circuits [J]. IEEE Trans on Power Electronics, 1991, 6(2):251-259.
  • 2黄胜利,周孝信.分布参数输电线路的时变动态相量模型及其仿真[J].中国电机工程学报,2002,22(11):1-5. 被引量:28
  • 3[3]Stankovic A M, Mattavelli P, Caliskan V, et al. Modeling and analysis of FACTS devices with dynamic phasors[A]. IEEE Power Engineering Society Winter Meeting, 2000. , Singapore[C], Jan. 2000, 2:1440-1446.
  • 4[4]Stefannov P C, Stankovic A M, Modeling of UPFC operation under unbalanced conditions with dynamic phasors [J]. IEEE Trans on Power Systems, 2002, 17(2):395-403.
  • 5[5]Stankovic A M, Sanders S R, Dynamic phasors in modeling and analysis of unbalanced polyphase AC machines [J]. IEEE Trans on Energy Conversion, 2002, 17(1):107-113.
  • 6[6]Shengli Huang, Xiaoxin Zhou, Analysis of balanced and unbalanced faults in power systems using dynamic phasors [A]. ICEE-PES/CSEE, POWERCON2002, Kunming[C], China, 2002.
  • 7[7]Wood A R, Arrillaga J, HVDC convertor waveform distortion: a frequency-domain analysis [J]. IEE Proc. Gener. Transm. Distrib , 1995, 142(1):88-96.
  • 8[8]Osauskas C M, Hume D J, Wood A R. Small signal frequency domain model of an HVDC converter [J]. IEE Proc. Gener. Transm. Distrib, 2001, 148(6):573-578.

二级参考文献6

  • 1Venmanian V, Schattler H, Zaborszky J. A time-delay differential algebraicp hasor formulation of the Large power system dynamics[R] in ISCAS 1994.
  • 2Electromagnetic Transients Program(EMTP) Rule Book[M].American EMTP User Group, Canacian,1982.
  • 3刘焕柳 (Liu Huanliu). 电力系统数字仿真(Digital simulation of electric power system) [M].重庆:四川大学出版社 (Chongqing:Si Chuan University Press).
  • 4Huang Shengli , Zhou X X .Bringing time-varying phasor into power system and modeling system components[C]. International Conference of Electric Engineer, Xi'an,2001.
  • 5Zaborszky J, Schattler H, Venmanian V. Limitations of the quasistationary dynamics and errordue to computations in network equation[C]. Power Systems Compu tation Conference, Avignon France, Aug. 1993.
  • 6Demarco C L, Verghese G.C. Bringing into phasor dynamics into the power system load flow [C]. 25th North America Power Symposium, Washington,USA 1993.