A review is conducted about the application of the evaporative cooling technology in thermal power plants.Different case studies are considered,namely,evaporative air conditioners,evaporative cooling in direct air-coo...A review is conducted about the application of the evaporative cooling technology in thermal power plants.Different case studies are considered,namely,evaporative air conditioners,evaporative cooling in direct air-cooled systems,gas turbine inlet cooling,wet cooling towers,and hybrid cooling towers with a crosswind effect.Some effort is provided to describe the advantages related to direct evaporative cooling when it is applied in thermal power plants and illustrate the research gaps,which have not been filled yet.In particular,typical case studies are intentionally used to compare the cooling performances when direct evaporative cooling is implemented in different types of cooling towers,including the natural draft wet cooling tower(NDWCT)and the pre-cooled natural draft dry cooling tower(NDDCT).It is shown that the NDWCT provides the best cooling performance in terms of power station cooling,followed by the pre-cooled NDDCT,and the NDDCT;moreover,the evaporative pre-cooling is able to enhance the cooling performance of NDDCT.Besides,on a yearly basis,better NDDCT cooling performances can be obtained by means of a spray-based pre-cooling approach with respect to wet media pre-cooling.Therefore,the use of nozzle spray is suggested for improvement in the performance of indirect/direct air-cooling systems with controlled water consumption.展开更多
In recent years,water collecting systems,with the associated advantages of energy saving and noise reduction,have become the foundation for the development of a scheme to optimize the structure of cooling towers.To ex...In recent years,water collecting systems,with the associated advantages of energy saving and noise reduction,have become the foundation for the development of a scheme to optimize the structure of cooling towers.To explore the feasibility of this approach for mechanical draft cooling towers,a small-scale experimental device has been built to study the resistance and splash performances of three U-type water collecting devices(WCDs)for different water flow rates and wind speeds.The experimental results show that within the considered ranges of wind speed and water flow rate,the pressure drop of the different WCDs can vary significantly.The resistance and local splash performances can also be remarkably different.Some recommendations about the most suitable system are provided.Moreover,a regression analysis of the experimental data is conducted,and the resulting fitting formulas for resistance and splash performance of WCD are reported.展开更多
Pre-cooling the inlet air of a dry cooling tower by means of a spray can improve the tower performance during periods of high temperature.To study the spray effect on the thermal performance of natural draft dry cooli...Pre-cooling the inlet air of a dry cooling tower by means of a spray can improve the tower performance during periods of high temperature.To study the spray effect on the thermal performance of natural draft dry cooling towers(NDDCTs),in this study 3-D numerical simulations of such a process have been conducted using Fluent 16.2(a two-way coupled Eulerian-Lagrangian approach).The considered NDDCT is 120 m high and only half system is simulated due to its structural symmetry.Three different spray strategies have been investigated at a typical crosswind speed of 4 m/s,which is the most frequent wind speed.The results have shown that:(1)The three implemented spray strategies can improve the thermal performance of the studied NDDCT with a vary-ing degree of success.In one case,the heat rejection rate can be increased by 35.2%,and the tower outlet water temperature can be decreased by 2.1℃ when compared with the no spray case;(2)To improve the thermal per-formance of the NDDCT using a small amount of water,the design of the spray pre-cooling system must include more nozzles on the windward and fewer or even no nozzles on the leeward sides of the NDDCT.展开更多
Flow channels with a variable cross-section are important components of piping system and are widely used in variousfields of engineering.Using afinite element method and modal analysis theory,flow-induced noise,mode ...Flow channels with a variable cross-section are important components of piping system and are widely used in variousfields of engineering.Using afinite element method and modal analysis theory,flow-induced noise,mode shapes,and structure-borne noise in such systems are investigated in this study.The results demonstrate that the maximum displacement and equivalent stress are located in the part with variable cross-sectional area.The aver-age excitation force on theflow channel wall increases with theflow velocity.The maximum excitation force occurs in the range of 0–20 Hz,and then it decreases gradually in the range of 20–1000 Hz.Additionally,as theflow velocity rises from 1 to 3 m/s,the overall sound pressure level associated with theflow-induced noise grows from 49.37 to 66.37 dB.Similarly,the overall sound pressure level associated with the structure-borne noise rises from 40.27 to 72.20 dB.When theflow velocity is increased,the increment of the structure-borne noise is higher than that of theflow-induced noise.展开更多
Numerical simulation are conducted to explore the characteristics of the axial inflow and related aerodynamic noise for a large-scale adjustable fan with the installation angle changing from−12°to 12°.In suc...Numerical simulation are conducted to explore the characteristics of the axial inflow and related aerodynamic noise for a large-scale adjustable fan with the installation angle changing from−12°to 12°.In such a range the maximum static(gauge)pressure at the inlet changes from−2280 Pa to 382 Pa,and the minimum static pressure decreases from−3389 Pa to−8000 Pa.As for the axial intermediate flow surface,one low pressure zone is located at the junction of the suction surface and the hub,another is located at the suction surface close to the casing position.At the outlet boundary,the low pressure is negative and decreases from−1716 Pa to−4589 Pa.The sound pressure level of the inlet and outlet noise tends to increase monotonously by 11.6 dB and 7.3 dB,respectively.The acoustic energy of discrete noise is always higher than that of broadband noise regardless of whether the inlet or outlet flow surfaces are considered.The acoustic energy ratio of discrete noise at the inlet tends to increase from 0.78 to 0.93,while at the outlet it first decreases from 0.79 to 0.73 and then increases to 0.84.展开更多
基金supported by the Shandong Natural Science Foundation(Grant No.ZR2022ME008)the Shandong Provincial Science and Technology SMEs Innovation Capacity Improvement Project(2022TSGC2018)+3 种基金the Shenzhen Science and Technology Program(KCXFZ20201221173409026)The financial supports from the“Young Scholars Program of Shandong University”(YSPSDU,No.2018WLJH73)the Open Project of State Key Laboratory of Clean Energy Utilization,Zhejiang University(Program Number ZJUCEU2020011)the Shandong Natural Science Foundation(Grant No.ZR2021ME118)are gratefully acknowledged。
文摘A review is conducted about the application of the evaporative cooling technology in thermal power plants.Different case studies are considered,namely,evaporative air conditioners,evaporative cooling in direct air-cooled systems,gas turbine inlet cooling,wet cooling towers,and hybrid cooling towers with a crosswind effect.Some effort is provided to describe the advantages related to direct evaporative cooling when it is applied in thermal power plants and illustrate the research gaps,which have not been filled yet.In particular,typical case studies are intentionally used to compare the cooling performances when direct evaporative cooling is implemented in different types of cooling towers,including the natural draft wet cooling tower(NDWCT)and the pre-cooled natural draft dry cooling tower(NDDCT).It is shown that the NDWCT provides the best cooling performance in terms of power station cooling,followed by the pre-cooled NDDCT,and the NDDCT;moreover,the evaporative pre-cooling is able to enhance the cooling performance of NDDCT.Besides,on a yearly basis,better NDDCT cooling performances can be obtained by means of a spray-based pre-cooling approach with respect to wet media pre-cooling.Therefore,the use of nozzle spray is suggested for improvement in the performance of indirect/direct air-cooling systems with controlled water consumption.
基金This work was supported by the Shandong Natural Science Foundation(Grant No.ZR2022ME008)the Shenzhen Science and Technology Program(KCXFZ20201221173409026)+2 种基金the Young Scholars Program of Shandong University(YSPSDU,No.2018WLJH73)the Open Project of State Key Laboratory of Clean Energy Utilization,Zhejiang University(Program No.ZJUCEU2020011)the Shandong Natural Science Foundation(Grant No.ZR2021ME118).
文摘In recent years,water collecting systems,with the associated advantages of energy saving and noise reduction,have become the foundation for the development of a scheme to optimize the structure of cooling towers.To explore the feasibility of this approach for mechanical draft cooling towers,a small-scale experimental device has been built to study the resistance and splash performances of three U-type water collecting devices(WCDs)for different water flow rates and wind speeds.The experimental results show that within the considered ranges of wind speed and water flow rate,the pressure drop of the different WCDs can vary significantly.The resistance and local splash performances can also be remarkably different.Some recommendations about the most suitable system are provided.Moreover,a regression analysis of the experimental data is conducted,and the resulting fitting formulas for resistance and splash performance of WCD are reported.
基金supported by the Shandong Provincial Science and Technology SMEs Innovation Capacity Improvement Project(2022TSGC2018)the Shandong Natural Science Foundation(Grant No.ZR2022ME008)+3 种基金the Shenzhen Science and Technology Program(KCXFZ20201221173409026)the“Young Scholars Program of Shandong University”(YSPSDU,No.2018WLJH73)the Open Project of State Key Laboratory of Clean Energy Utilization,Zhejiang University(Program Number ZJUCEU2020011)the Shandong Natural Science Foundation(Grant No.ZR2021ME118).
文摘Pre-cooling the inlet air of a dry cooling tower by means of a spray can improve the tower performance during periods of high temperature.To study the spray effect on the thermal performance of natural draft dry cooling towers(NDDCTs),in this study 3-D numerical simulations of such a process have been conducted using Fluent 16.2(a two-way coupled Eulerian-Lagrangian approach).The considered NDDCT is 120 m high and only half system is simulated due to its structural symmetry.Three different spray strategies have been investigated at a typical crosswind speed of 4 m/s,which is the most frequent wind speed.The results have shown that:(1)The three implemented spray strategies can improve the thermal performance of the studied NDDCT with a vary-ing degree of success.In one case,the heat rejection rate can be increased by 35.2%,and the tower outlet water temperature can be decreased by 2.1℃ when compared with the no spray case;(2)To improve the thermal per-formance of the NDDCT using a small amount of water,the design of the spray pre-cooling system must include more nozzles on the windward and fewer or even no nozzles on the leeward sides of the NDDCT.
基金supported by the Key Research and Development Project of Shandong Province[2019GSF109084]the National Natural Science Foundation of China[51776111]Young Scholars Program of Shandong University[2018WLJH73].
文摘Flow channels with a variable cross-section are important components of piping system and are widely used in variousfields of engineering.Using afinite element method and modal analysis theory,flow-induced noise,mode shapes,and structure-borne noise in such systems are investigated in this study.The results demonstrate that the maximum displacement and equivalent stress are located in the part with variable cross-sectional area.The aver-age excitation force on theflow channel wall increases with theflow velocity.The maximum excitation force occurs in the range of 0–20 Hz,and then it decreases gradually in the range of 20–1000 Hz.Additionally,as theflow velocity rises from 1 to 3 m/s,the overall sound pressure level associated with theflow-induced noise grows from 49.37 to 66.37 dB.Similarly,the overall sound pressure level associated with the structure-borne noise rises from 40.27 to 72.20 dB.When theflow velocity is increased,the increment of the structure-borne noise is higher than that of theflow-induced noise.
基金supported by Key Research and Development Project of Shandong Province[2019GSF109084]Young Scholars Program of Shandong University[2018WLJH73].
文摘Numerical simulation are conducted to explore the characteristics of the axial inflow and related aerodynamic noise for a large-scale adjustable fan with the installation angle changing from−12°to 12°.In such a range the maximum static(gauge)pressure at the inlet changes from−2280 Pa to 382 Pa,and the minimum static pressure decreases from−3389 Pa to−8000 Pa.As for the axial intermediate flow surface,one low pressure zone is located at the junction of the suction surface and the hub,another is located at the suction surface close to the casing position.At the outlet boundary,the low pressure is negative and decreases from−1716 Pa to−4589 Pa.The sound pressure level of the inlet and outlet noise tends to increase monotonously by 11.6 dB and 7.3 dB,respectively.The acoustic energy of discrete noise is always higher than that of broadband noise regardless of whether the inlet or outlet flow surfaces are considered.The acoustic energy ratio of discrete noise at the inlet tends to increase from 0.78 to 0.93,while at the outlet it first decreases from 0.79 to 0.73 and then increases to 0.84.