Stability Analysis of Closed-loop Water System 被引量:1
1
作者 Yongzheng FU Keqi WU yaqiao cai 《Journal of Thermal Science》 SCIE EI CAS CSCD 2006年第2期152-158,共7页
Aiming at closed-loop water system, by the method that shutting certain subcircuit, and solving the piping network, computing flow deviation of other subcircuits, then analyzing the rules of variation of stability wit... Aiming at closed-loop water system, by the method that shutting certain subcircuit, and solving the piping network, computing flow deviation of other subcircuits, then analyzing the rules of variation of stability with various factors, following conclusions are obtained: When reducing the resistance in main pipes, increasing resistance of subcircuits, system stability can be improved. Centralized regulation by changing power has no influence on system stability; centralized regulation by changing resistances will decrease system stability. Pump characteristics curve influences system stability, stability of the flat characteristic is superior to the steep one. For direct return system (DRS), the stability of subcircuit which is farthest from the heat source is the worst. For reverse return system (RRS), the stability of subcircuit in the middle of the pipe-network has the worst stability. Overall, stability of RRS is inferior to that of DRS. 展开更多
关键词 closed-loop water system stability flow deviation direct return system reverse return system