期刊文献+
共找到4篇文章
< 1 >
每页显示 20 50 100
Simulation Studies of an Integrated Overcurrent Relay Protection Scheme for Distribution Systems 被引量:2
1
作者 Z.Q. Bo X.Z. Dong +1 位作者 B.H. Zhang J.H. He 《Journal of Energy and Power Engineering》 2011年第1期55-62,共8页
This paper presents an integrated protection technique for power distribution systems. A novel integrated protection scheme based on overcurrent protection technique for distribution system is described, in which a sp... This paper presents an integrated protection technique for power distribution systems. A novel integrated protection scheme based on overcurrent protection technique for distribution system is described, in which a specially designed protection relay is installed at each substation of a network and responsible for the protection of every line sections connected to the substation busbar The conventional directional overcurrent and the new adaptive accelerated protection algorithms with multiple settings are implemented into the relay to cover all the protected line sections. The paper includes studies of a typical multi section distribution network to demonstrate the principle of the scheme. Studies show that the new scheme not only offer the new protection features for individual power line section, but also provide the characteristics of integrated protection. 展开更多
关键词 Overcurrent protection integrated protection centralized protection network protection digital substation powersystem simulation.
下载PDF
Impact of Sensor Technology for Line Protection Performance
2
作者 Jianping Wang Murari Saha Torbjom Enairsson 《Journal of Energy and Power Engineering》 2014年第4期716-723,共8页
The paper has presented the impact on the line protection performance with the introduction of MUs (merging units) in the process bus level. The paper begins with the introduction on modem digital substation structu... The paper has presented the impact on the line protection performance with the introduction of MUs (merging units) in the process bus level. The paper begins with the introduction on modem digital substation structure and process bus. Then, the paper describes the performances of different sensors such as CTs (current transformers), CVTs (capacitive voltage transformers), FOCS (fiber optical current transducers) and FOVS (fiber optical voltage transducers). With the use of above transducers together with MUs, the performance of distance protection function and line differential protection function have been investigated and presented. Finally, conclusions based on the study are presented in the paper. 展开更多
关键词 Distance protection line differential protection current transformer voltage transformer digital substation non-conventional transformer.
下载PDF
Efficient maintenance testing in digital substations based on IEC 61850 edition 2 被引量:9
3
作者 Alexander Apostolov 《Protection and Control of Modern Power Systems》 2017年第1期406-419,共14页
Digital substations are mostly important in the future of the electric power industry which makes their testing a critical process to ensure the required reliability and security of the grid.The paper introduces the d... Digital substations are mostly important in the future of the electric power industry which makes their testing a critical process to ensure the required reliability and security of the grid.The paper introduces the definition of a digital substation and efficient testing,as well as the requirements for isolation during testing.It later describes testing related features in IEC 61850 Edition 2 and testing methods that can be used in digital substations.Maintenance testing examples and testing tools requirements are also presented.And remote testing principles are described at the end of the paper.The proposed remote testing by controlling the test system in a remote substation from the convenience of the engineering office brings significant benefits by improving efficiency and safety,as well as reducing outage times. 展开更多
关键词 Digital substation Maintenance testing IEC 61850
下载PDF
Integrated Wide Area Protection and Control for Power Grid Security 被引量:5
4
作者 Qingping Wang Zhiqian Bo +4 位作者 Yingke Zhao Xiaowei Ma Ming Zhang Hao Zheng Lin Wang 《CSEE Journal of Power and Energy Systems》 SCIE CSCD 2019年第2期206-214,共9页
The traditional“three defense lines”for power systems are based on local information and static protection&control strategy,which are not suitable to modern large-scale power systems.In order to improve the secu... The traditional“three defense lines”for power systems are based on local information and static protection&control strategy,which are not suitable to modern large-scale power systems.In order to improve the security of UHV hybrid power grids,the Integrated Wide Area Protection&Control(IWAPC)is proposed in this paper by applying the new technologies of synchronized high-speed communication,which integrates“three defense lines”and promotes existing wide area protection only for security control.The IWAPC is the hierarchical protection and control system which provides the protection and control for wide area power networks to improve their reliability and security.It is divided into three levels,the local bay level,the substation integrated protection level and the wide area protection level.The wide area real-time protection and control information platform is the most important part of the IWAPC,which is based on a synchronized wide area communication network.The key technologies and new development trends include network topology analysis,wide area backup protection,wide area intelligent reclosing,wide area load shedding,wide area auto-switching,overload cutoff and transfer,transmission section protection,intelligent system splitting and dynamic stability control.It cannot only integrate three lines of defense for power system protection and control,but also improve security of the power grid. 展开更多
关键词 Digital substation power grid security control system protection wide area protection&control
原文传递
上一页 1 下一页 到第
使用帮助 返回顶部